Subject to modifications and errors
Page 36 of 71
2019-06-26 edition
.035
ULN >> off
U
THR
OFF
%Unom
125
100
130
100
135
U
THR
ON
Fixed Hysteresis (1% U
NOM
)
.037
T ULN >>
Time OFF
ms
100
100
100
100
10000
Only active for:
Connection Modes: 2-wire, 4-wire (LN)
Undervoltage2 Line to Neutral
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.039
ULN << off
U
THR
OFF
%Unom
30
10
100
10
100
.040
ULN << on
U
THR
ON
%Unom
95
95
95
10
100
.041
T ULN <<
Time OFF
ms
800
800
800
50
60000
Only active for:
Connection Modes: 2-wire, 4-wire (LN)
Overfrequency1
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.055
f > off
f
THR
OFF
Hz
51,5
50,0
55,0
50,0
55,0
.056
f > on
f
THR
ON
Hz
50,1
50,1
50,1
50,0
55,0
.057
T f >
Time OFF
ms
5000
150
5000
150
10000
Underfrequency1
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.059
f < off
f
THR
OFF
Hz
47,50
45,0
50,0
45,0
50,0
.060
f < on
f
THR
ON
Hz
49,9
49,9
49,9
45,0
50,0
.061
T f <
Time OFF
ms
50
50
70
50
10000
Overfrequency2
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.063
f >> off
f
THR
OFF
Hz
52,5
50,0
55,0
50,0
55,0
.064
f >> on
f
THR
ON
Hz
50,1
50,1
50,1
50,0
55,0
.065
T f >>
Time OFF
ms
50
50
70
50
10000
Auxiliary Contact type
Conformity Range
Possible Range
ID
Default
.099
Contact
dis. (disabled)
n.o. (normally opened)
n.c. (normally closed)
dis. (disabled)
n.o. (normally opened)
n.c. (normally closed)
dis. (disabled)
Turn on Delay
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.102
T on delay
s
60
0
60
0
1800
Device Information
ID
.105 ID: xxxxxx
SW: aa.dd.ccb
xxxxx = Device ID
dd: Software version of Display Software
aa: Software version of Measuring Software
cc: Index of Configuration set
b: Version of Configuration set
Password
ID
Default
Min
Max
.106
PW1
1
st
digit of Password
0
0
9
.107
PW2
2
nd
digit of Password
0
0
9
.108
PW3
3
rd
digit of Password
0
0
9