Subject to modifications and errors
Page 38 of 71
2019-06-26 edition
.069
T U/F st 2
Time OFF
ms
500
500
500
50
300000
f
THR
ON
Fixed Hysteresis (0,05 Hz)
Rate of Change of Frequency (RoCoF)
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.090
RoCoF
Enable Function
On
on / off
on / off
.091
RoCoF off
RoCoF
THR
OFF
mHz/s
1000
10
3000
10
3000
.092
RoCoF on
RoCoF
THR
ON
mHz/s
950
10
3000
10
3000
.093
RoCoFDelay Time OFF
ms
500
50
500
50
2000
Window
Fixed window length 225ms
Phase Shift (PShift)
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.094
PShift
Enable Function
Off
on / off
on / off
.095
PShift off
PShift
THR
OFF
°
12
--
--
3
15
.096
PShift on
PShift
THR
ON
°
9
--
--
3
15
Window
Fixed window length 200ms
Auxiliary Contact type
Conformity Range
Possible Range
ID
Default
.099
Contact
dis (disabled)
n.o. (normally opened)
n.c. (normally closed)
dis. (disabled)
n.o. (normally opened)
n.c. (normally closed)
dis. (disabled)
Turn on Delay
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.102
T on delay
s
20
20
20
0
600
Device Information
ID
.105 ID: xxxxxx
SW: aa.dd.ccb
xxxxx = Device ID
dd: Software version of Display Software
aa: Software version of Measuring Software
cc: Index of the Configuration set
b: Version of the Configuration set
Password
ID
Default
Min
Max
.106
PW1
1
st
digit of Password
0
0
9
.107
PW2
2
nd
digit of Password
0
0
9
.108
PW3
3
rd
digit of Password
0
0
9
.109
PW4
4
th
digit of Password
0
0
9
Remark:
If all 4 digits of the Password are 0 (default setting) the Password request is skipped