Subject to modifications and errors
Page 13 of 71
2019-06-26 edition
3.3.5
VDE-AR-N 4105 (inverter)
•
Selectable feedback contact (normally closed / normally open)
•
1 Overvoltage threshold - phase to phase voltage
•
2 undervoltage thresholds - phase to phase voltage
•
1 Overvoltage threshold - phase-to-neutral voltage
•
2 undervoltage thresholds - phase-to-neutral voltage
•
10-minute average Overvoltage threshold
•
1 Overfrequency threshold
•
1 Underfrequency threshold
•
1 random over-frequency threshold (can be activated if required)
•
switch-on delay
•
random switch-on delay (can be activated if required)
3.3.6
VDE-AR-N 4110 (tested according to TR3, evaluation report TR8)
•
Selectable connection mode (1 phase, 3 phase)
•
Selectable nominal voltage
•
Selectable feedback contact (normally closed / normally open)
•
2 Overvoltage thresholds - phase to phase voltage (automatic selection depending on Connection
Mode)
•
2 undervoltage thresholds - phase to phase voltage (automatic selection depending on Connection
Mode)
•
2 Overvoltage thresholds - phase-to-neutral voltage (automatic selection depending on Connection
Mode)
•
2 undervoltage thresholds - phase-to-neutral voltage (automatic selection depending on
Connection Mode)
•
2 over-frequency thresholds
•
1 Underfrequency threshold
•
switch-on delay
3.3.7
G99/1/3 LV (low voltage)
•
Selectable nominal voltage
•
Selectable feedback contact (normally closed / normally open)
•
2 overvoltage thresholds - phase-to-neutral voltage
•
1 Undervoltage threshold - phase-to-neutral voltage
•
1 Overfrequency threshold
•
2 under-frequency thresholds
•
1 Frequency ramp threshold (RoCoF ... can be activated if required)
•
1 phase jump threshold (PShift ... can be deactivated if required)
•
switch-on delay
3.3.8
G99/1/3 HV (medium/high voltage)
•
Selectable nominal voltage
•
Selectable feedback contact (normally closed / normally open)
•
2 overvoltage thresholds - phase to phase voltage
•
1 Undervoltage threshold - phase to phase voltage
•
1 Overfrequency threshold
•
2 under-frequency thresholds
•
1 Frequency ramp threshold (RoCoF ... can be activated if required)
•
1 phase jump threshold (PShift ... can be deactivated if required)
•
switch-on delay
3.3.9
G98/1/2
•
Selectable nominal voltage
•
Selectable feedback contact (normally closed / normally open)
•
2 overvoltage thresholds - phase-to-neutral voltage
•
1 Undervoltage threshold - phase-to-neutral voltage
•
1 Overfrequency threshold
•
2 under-frequency thresholds
•
1 Frequency ramp threshold (RoCoF ... can be activated if required)