Subject to modifications and errors
Page 34 of 71
2019-06-26 edition
Underfrequency1
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.059
f < off
f
THR
OFF
Hz
47,50
47,50
47,50
47,50
47,50
.060
f < on
f
THR
ON
ms
47,50
47,50
47,50
47,50
50,00
Time OFF
Fixed to a fastest possible disconnection
Comment:
f < on has a fixed offset of 0,025 Hz added to the displayed value
Random over frequency
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.086
f > random
Enable function
off
on … off
on … off
.087
f > random
f
THR
OFF
Hz
50.20
51.50
50.20
51.50
Time OFF
Fixed to a fastest possible disconnection
Comment:
The random threshold value is shown in .087 and cannot be edited
Auxiliary Contact type
Conformity Range
Possible Range
ID
Default
.099
Contact
n.c. (normally closed)
n.o. (normally opened)
n.c. (normally closed)
n.o. (normally opened)
n.c. (normally closed)
dis. (disabled)
Turn on Delay
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.102
T on delay
s
60
60
60
0
600
Random Turn on delay
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.103
Ton random
Enable function
off
on … off
on … off
.104
Ton random
Turn on time
s
60
600
60
600
Comment:
The random time value is shown in .104 and cannot be edited
Device Information
ID
.105 ID: xxxxxx
SW: aa.dd.ccb
xxxxx = Device ID
dd: Software version of Display Software
aa: Software version of Measuring Software
cc: Index of the Configuration set
b: Version of the Configuration set
Password
ID
Default
Min
Max
.106
PW1
1
st
digit of Password
4
0
9
.107
PW2
2
nd
digit of Password
1
0
9
.108
PW3
3
rd
digit of Password
0
0
9
.109
PW4
4
th
digit of Password
5
0
9
Remark:
If all 4 digits of the Password are 0 (default setting) the Password request is skipped