Subject to modifications and errors
Page 47 of 71
2019-06-26 edition
3.7.12
E 8001/8101
Connection Mode
Conformity Range
Possible Range
ID
Default
.003
Connection
4-wire (LN+LL)
4-wire (LN+LL)
2-wire, 3-wire, 4-wire (LN),
4-wire(LN+LL)
Nominal Voltage
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.005
ULN/LL nom
Unom Y
Unom Δ
V
V
230.0
400.0
71.00
100.0
230.0
400.0
35.0
50.0
241.4
420.0
Overvoltage1 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.011
ULLmax1off
U
THR
OFF
%Unom
115
115
115
100
135
.012
ULLmax1on
U
THR
ON
%Unom
110
110
110
100
135
.013
T ULL max1
Time OFF
ms
50
50
180000
50
180000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Undervoltage1 Line to Line
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.015
ULLmin1off
U
THR
OFF
%Unom
80
80
80
10
100
.016
ULLmin1on
U
THR
ON
%Unom
90
90
90
10
100
.017
T ULL min1
Time OFF
ms
50
50
180000
50
180000
Only active for:
Connection Modes: 3-wire, 4-wire (LN+LL)
Overvoltage1 Line to Neutral
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.019
ULNmax1off
U
THR
OFF
%Unom
115
115
115
100
135
.020
ULNmax1on
U
THR
ON
%Unom
110
110
110
100
135
.021
T ULN max1
Time OFF
ms
50
50
180000
50
180000
Only active for:
Connection Modes: 2-wire, 4-wire (LN)
Undervoltage1 Line to Neutral
Conformity Range
Possible Range
ID
Default
Min
Max
Min
Max
.023
ULNmin1off
U
THR
OFF
%Unom
80
80
80
10
100
.024
ULNmin1on
U
THR
ON
%Unom
90
90
90
10
100