65
Step 1: Before Continuing with Troubleshooting
WARNING!
All electric power should be disconnected and you should have already made
sure that the compressor does not have a ground fault (see “Checking for a Ground Fault”
on pages 40-41).
You should have also checked the windings for continuity and proper
resistance (see “Checking for Continuity and Proper Resistance” on page 42, made sure
the system is getting proper voltage, and that the control, thermostat, and contactor are
working properly.
NOTE: the compressor housing MUST be at 130°F or less for the following checks. This
temperature can be read by Tempstik or is that temperature which will allow the hand to
remain in contact with the compressor housing without discomfort.
Step 2: Check Internal Thermal Protector
If there is continuity between all terminals the thermal protector should be good. If R to S
has continuity and R to C and S to C do not, the thermal protector may be tripped. Wait
for the protector to cool off and close. This may take more than an hour. Check continuity
gain. If there is no continuity, replace the compressor.
Step 3: Check Run Capacitor
CAUTION: using a 20,000 ohm resistor, discharge the capacitor before removing it from
the system to avoid damage to measuring devices and risk of electric shock. Disconnect
the run capacitor from the system. Use a capacitance meter to check capacitor. Capaci-
tance should be 10% of the marked capacitor value.
As an alternative, check the run capacitor by measuring continuity across the capacitor
terminals:
•
Rx1 scale: If there is continuity, then the run capacitor is shorted and needs to be
replaced.
•
Rx100,000 scale: If there is no needle deflection on an analog meter or if a digital meter
indicates infinite resistance, then the run capacitor is open and needs to be replaced.
Possible reasons that a run capacitor is not working properly include:
•
Use of incorrect run capacitor.
Replace with proper run capacitor.
•
Line voltage is too high
(greater than 100% of rated voltage).
Step 4: Reconnect Run Capacitor
Reconnect the run capacitor into circuit at terminals S and R. (Marked terminal should go
to R.)
Step 5: Continue Troubleshooting
If all above tests prove satisfactory and unit still fails to operate properly, check for ad-
equate compressor pumping as outlined in the procedure on page 70.
Summary of Contents for AH5540E
Page 1: ...Hermetic Compressor Service Handbook Wholesale Distribution North America...
Page 2: ......
Page 3: ...Hermetic Compressor Service Handbook Ann Arbor MI 48108 REV 3 11...
Page 4: ......
Page 8: ......
Page 9: ...Chapter 1 General Service Safety Precautions...
Page 16: ......
Page 17: ...Chapter 2 Model and Application...
Page 22: ......
Page 23: ...Chapter 3 Compressor Motor and Component...
Page 36: ......
Page 37: ...Chapter 4 Servicing...
Page 38: ...30 SERVICE HANDBOOK...
Page 79: ...71...
Page 80: ......
Page 81: ...Chapter 5 Installation and Replacement...
Page 96: ......
Page 97: ...Liquid refrigerant migration to compressor FIGURE 6 1 Chapter 6 Operation...
Page 108: ......
Page 109: ...Appendix...
Page 113: ...105 Reciprocating Compressor FIGURE A 2 Internal view of typical air conditioning compressor...
Page 118: ...110 SERVICE HANDBOOK Notes...
Page 119: ......