COMBUSTION AIR
The air treatment unit is to be installed as provided for by the Standards in force; the unit is to be used only
in sufficiently aired places.
Always ensure that the combustion air socket is not clogged (ex. must be free from leaves, pieces of paper,
nylon strips, etc.).
Adequate ventilation openings must be available, as provided for by applicable Standards
GAS SUPPLY LINE
The gas supply line must be installed by an expert and competent person who performs the work as
provided for by applicable Standards, Laws and Regulations.
FIXED PROTECTIONS
To prevent the accidental contact with the appliance mobile parts, check that the fixed protections have
been properly fixed.
The air outlet and inlet ducts must be installed in order to avoid contact with the moving parts and/or
hazardous areas in the equipment.
GAS BURNER AND RELEVANT SUPPLY RAMP
Gas burner and supply ramp combination (supplied dismantled and in separate packages):
GAS BURNER
TYPE 1
TYPE 2
Brand
RIELLO
RIELLO
Model
mod
BS 3/M
RS 34/M MZ
Version
MODULATING
MODULATING
Plate work field
kW
48-79/195
70/125-390
GAS RAMP
TYPE 1
TYPE 2
Brand
RIELLO
RIELLO
Model
mod
CG 220
MB 12/1
Gas inlet fitting
inches
¾“
1“
¼
The gas minimum supply pressure must be enough to compensate for the supply ramp load loss
plus safety coefficient of about 30%.
The gas supply pressure must be stable and never exceed the maximum value mentioned in the
burner guidelines.