background image

GB

17

• By calling the telephone line on which the 

TYPHONE

is recorded, the user can:

- know the ambient temperature of zone 1,
- know the setpoint temperature of the current mode of zone 1,
- send an override setpoint.

In case of setpoint modification, zone 1 and possible zone 2 operates in “COMFORT” mode.

This override is indicated by an index on the LCD.
Any action on the rotary knob deactivates the override and extinguishes the indicator.

• Parameters possibilities: 

- access code change (parameter 62),
- interface language change - French / English (parameter 61).

8.10 - POWER FAILURE

• In case of power failure, the parameters and settings are maintained. If the power outage exceeds 6 hours, the time setting

will have to be corrected.

8.11 - MISCELLANEOUS

• Mode changes using the rotary knob (

Heating / Cooling

(not used)

/ Anti-freeze / Stop

) are delayed 10 seconds in order to

filter inappropriate actions. However, the "

Time Setting

" and "

Hourly Programming

" positions do not have the time delay

feature.

• The authorization thresholds on the water temperature are cut-off values with a differential of 1K for the reset.

9.1 - STARTING

9.1.1 - PRELIMINARY CHECKS

Check:
• Ensure that the hydraulic connections are properly tight and that the hydraulic system operates correctly:

- purge of circuits, valve position, hydraulic pressure (1.5 to 3 bar).

• For leaks.
• Electrical cables and wires are well secured to their connection terminals. Loose terminals can cause heat build-up on

the terminal board and malfunctions.

• Ensure that the electric cables are properly protected from all sheet metal edges or metal parts that could damage them.
• Ensure that control cables and power cables are properly separated.
• Check that the unit is properly grounded.
• For tools or foreign objects in the units and control box.
• The correct installation of the heat pump and boiler. These elements must be ready to operate. Refer to the

corresponding manuals.

9.1.2 - CONTROL PARAMETERISATION

• Parameterisation is performed on the control box.
• Set the button on the installation's control box to “

OFF

”.

• Check the parameterisation and, if required, adapt it to the type of application and according to the installation conditions

(see paragraph 8.7).

9.1.3 - ADDITIONAL CHECKS

• With the control box button on “

OFF

”, turn installation power on.

• Force operation of the installation's circulating pump.
• Make sure that the generator's circulator is operating and adjust the water output as required (with the control valve).
• Check that water is properly circulating in the installation (valve position).
• Make sure to purge the circuits and check the hydraulic pressure.
• Make sure that the generator has started in the desired mode.
• Make sure that the supplementary valve is operating, possibly by forcing the opening.
• Check the generator and boiler setpoints.
• Check the indications of the temperature sensors; perform an “

Offset

” calibration of these sensors if required.

.

9 - STARTING - MAINTENANCE

Before doing any work on the installation, make sure it is switched off and all power supplies locked out.
Any work must be carried out by personnel qualified and authorised to work on this type of machine.

IMPORTANT NOTE

Summary of Contents for K 60 D 066 Z

Page 1: ...EGRAZIONE APPLICAZIONE 1 ZONA RADIATORI AZIONE TUTTO O NIENTE KIT DE REGULACI N PARA BOMBA DE CALOR CON CONEXI N DE CALDERA APLICACI N UNA ZONA RADIADORES ACCI N TODO O NADA SET STEUERMODUL UND SCHALT...

Page 2: ...aintenance of this kit must be performed by qualified and authorised personnel in accordance with current standards and recognized trade practices Before doing any work on the installation make sure i...

Page 3: ...cuit breaker 4 Terminal strip 5 Control board accessory location Bi PAC see specific installation manual 1 5 3 2 4 4 OPERATING PRINCIPLE The kit is designed allow complete installation control from th...

Page 4: ...coupling bottle Outside sensor 230 VAC power supply Installation according to current standards and recognised trade practices Dirt separator 70600114 Generator Note install the strainer filter suppli...

Page 5: ...l facing North North west and located away from parasitic heat sources chimney thermal bridge etc and sheltered from inclement weather under a roof overhand for example Connection as per paragraph 6 5...

Page 6: ...es do not route these cables near power cables A Generator load shedding signal if required Two possibilities 1 By a remote info signal coming from the electrical utility meter EDF French electrical u...

Page 7: ...d size 0 5 mm2 H Boiler supplementary valve control if any On Off control signal 230 V 50 Hz 30 VA maximum available on the box s terminal strip terminal 2 common connected to the Neutral terminal 1 v...

Page 8: ...ply 230 V 1 50 Hz Control unit Not used Water return temperature sensor Outside temperature sensor Printed Circuit Board Boiler authorisation Boiler fault contact unavailable as required Remove the br...

Page 9: ...e temperature and validation Liquid crystal display LCD Micro switch to activate a 2nd heating zone using electric convectors see paragraph 8 5 This micro switch is located on the back of the unit s p...

Page 10: ...ly Not used Boiler alarm input unavailable Not used Generator fault input Generator On Off output Generator H C output not used Outside temperature Installation return water temperature Potential free...

Page 11: ...int temperature of the zone adjustable from 15 to 25 C causes the resulting setpoint water temperature to decrease or increase of 2 degrees respectively However this variation cannot exceed 4 degrees...

Page 12: ...ope calculated according to the parameters of the control equipment is automatically corrected by the system by adding or subtracting a correcting coefficient the value of which is displayed in parame...

Page 13: ...ing mode with hourly programming the Comfort or ECO signals are transmitted to the 2nd zone according to the corresponding hourly programming Note In case of load shedding a shut down signal is transm...

Page 14: ...2 Go to parameter 70 Press the Z OK button the value of the parameter is displayed This value may be read or modified using the and buttons if the system is in the Stop position If parameters are modi...

Page 15: ...25 C 17 C 24 Lowering of ECO temperature ambiente T 1 6K 3K 25 Anti freeze ambiance setpoint T 8 18 C 12 C Water temperature settings 29 Water temperature setpoint in anti freeze mode return T 20 40...

Page 16: ...on the display Automatic reset the alarm disappears when the source of the fault is corrected Note The alarms are displayed even if the system is shutdown If several alarms occur simultaneously the v...

Page 17: ...lfunctions Ensure that the electric cables are properly protected from all sheet metal edges or metal parts that could damage them Ensure that control cables and power cables are properly separated Ch...

Page 18: ...hat all electrical connections are properly tight Check the ground connections Verification of the hydraulic circuit cleaning of the strainer filter and drip pan water quality purge pressure etc Verif...