Generator operating safety features in heating mode

- A safety device on the water temperature (installation return) prohibits generator operation if this temperature is

below the thermodynamic heating authorization threshold (parameter 36). In this case, only the boiler is authorised
to raise the water temperature and allow the generator to function, regardless of the outside temperature. The
activation of this safety feature is indicated by the flashing of the display.

- Generator operation is prohibited if the outside temperature is below the generator's shut-off threshold (parameter

20). Only the boiler is authorised.

8.1.3 - "ECONOMY" HEATING MODE 

• The switch to "

ECO

" mode lowers the ambient temperature setpoint by a value than can be adjusted from 1 to 6 °K

(parameter 24).

• Switching from "

Comfort

" to "

ECO

" is accomplished either by hourly programming, weekly programming by zone or by

actuating the rotary knob for the entire installation.

• In the case of hourly programming, the user can activate a temporary override (1 hour + periods of 1 hour during the

current day) per zone.

8.1.4 - "ANTI-FREEZE" HEATING MODE (prolonged absence) 

• Selection is made using the rotary knob on the control

unit for the entire installation.

• The resulting water temperature setpoint shifts to an

adjustable value via parameter 29. The heating
(gen boiler if required) is actuated according
to the ambient temperature setpoint, which can be
adjusted by parameter 25.

8.1.5 - SELF-ADAPTING HEATING SLOPE

• System activated by parameter 74 = 1.
• Principle: the theoretical slope calculated according to the parameters of the control equipment is automatically

corrected by the system by adding (or subtracting) a correcting coefficient (the value of which is displayed in parameter

90). This coefficient is determined by analysing, in terms of a 24-hour continuous operating period in "

Comfort

"

heating mode, the behaviour of the ambient temperature in relation to the setpoint temperature (in "

Comfort

" mode).

This analysis is also weighted by the difference between the setpoint and the outdoor temperature.

• Example:

(P) 

= Theoretical 

slope

(P + K)

=  Slope increased with ambient temperature

below the setpoint

(P - K)

=  Slope decreased with ambient

temperature above the setpoint

Note

Regardless of the slope, the resulting setpoint cannot
exceed the maximum temperature value of the water
(parameter 30) (possibly corrected according to the
ambient temperature).

Example:

To adjust the following parameters: 

. Parameter 21 = 0°C
. Parameter 23 = 20°C
. Parameter 30 = 60°C
. Parameter 32 = 30°C

Theoretic slope value 

P

=

= 1.50.

If the value of the coefficient 

K

read on parameter 90 is “10” (hundredths), the actual slope becomes: 

P

K

= 1.50 + 0.10 = 1.60.

The value of this coefficient is reset in the event of:

- deactivation of the system by parameter 74,
- re-initialisation of the parameters by parameter 60,
- an application change by parameter 70.

8.2 - COOLING MODE

Inactive
Note

: The selection of this mode, using the rotary knob, causes the system to shut down (“

OFF

”).

60 - 30

20 - 0

Ambient temperature

Heating command

Anti-freeze mode ambient temperature setpoint

(P+K)

(P-K)

(P)

Water temperature

Peak limiting

Max. water
temperature
(parameter 30)

Min. water
temperature
(parameter 32)

Regional min.
temperature
(parameter 21)

Heating authorisation
threshold
(parameter 23)

Outside
temperature

Summary of Contents for K 60 D 066 Z

Page 1: ...EGRAZIONE APPLICAZIONE 1 ZONA RADIATORI AZIONE TUTTO O NIENTE KIT DE REGULACI N PARA BOMBA DE CALOR CON CONEXI N DE CALDERA APLICACI N UNA ZONA RADIADORES ACCI N TODO O NADA SET STEUERMODUL UND SCHALT...

Page 2: ...aintenance of this kit must be performed by qualified and authorised personnel in accordance with current standards and recognized trade practices Before doing any work on the installation make sure i...

Page 3: ...cuit breaker 4 Terminal strip 5 Control board accessory location Bi PAC see specific installation manual 1 5 3 2 4 4 OPERATING PRINCIPLE The kit is designed allow complete installation control from th...

Page 4: ...coupling bottle Outside sensor 230 VAC power supply Installation according to current standards and recognised trade practices Dirt separator 70600114 Generator Note install the strainer filter suppli...

Page 5: ...l facing North North west and located away from parasitic heat sources chimney thermal bridge etc and sheltered from inclement weather under a roof overhand for example Connection as per paragraph 6 5...

Page 6: ...es do not route these cables near power cables A Generator load shedding signal if required Two possibilities 1 By a remote info signal coming from the electrical utility meter EDF French electrical u...

Page 7: ...d size 0 5 mm2 H Boiler supplementary valve control if any On Off control signal 230 V 50 Hz 30 VA maximum available on the box s terminal strip terminal 2 common connected to the Neutral terminal 1 v...

Page 8: ...ply 230 V 1 50 Hz Control unit Not used Water return temperature sensor Outside temperature sensor Printed Circuit Board Boiler authorisation Boiler fault contact unavailable as required Remove the br...

Page 9: ...e temperature and validation Liquid crystal display LCD Micro switch to activate a 2nd heating zone using electric convectors see paragraph 8 5 This micro switch is located on the back of the unit s p...

Page 10: ...ly Not used Boiler alarm input unavailable Not used Generator fault input Generator On Off output Generator H C output not used Outside temperature Installation return water temperature Potential free...

Page 11: ...int temperature of the zone adjustable from 15 to 25 C causes the resulting setpoint water temperature to decrease or increase of 2 degrees respectively However this variation cannot exceed 4 degrees...

Page 12: ...ope calculated according to the parameters of the control equipment is automatically corrected by the system by adding or subtracting a correcting coefficient the value of which is displayed in parame...

Page 13: ...ing mode with hourly programming the Comfort or ECO signals are transmitted to the 2nd zone according to the corresponding hourly programming Note In case of load shedding a shut down signal is transm...

Page 14: ...2 Go to parameter 70 Press the Z OK button the value of the parameter is displayed This value may be read or modified using the and buttons if the system is in the Stop position If parameters are modi...

Page 15: ...25 C 17 C 24 Lowering of ECO temperature ambiente T 1 6K 3K 25 Anti freeze ambiance setpoint T 8 18 C 12 C Water temperature settings 29 Water temperature setpoint in anti freeze mode return T 20 40...

Page 16: ...on the display Automatic reset the alarm disappears when the source of the fault is corrected Note The alarms are displayed even if the system is shutdown If several alarms occur simultaneously the v...

Page 17: ...lfunctions Ensure that the electric cables are properly protected from all sheet metal edges or metal parts that could damage them Ensure that control cables and power cables are properly separated Ch...

Page 18: ...hat all electrical connections are properly tight Check the ground connections Verification of the hydraulic circuit cleaning of the strainer filter and drip pan water quality purge pressure etc Verif...

Page 19: ...GB 19...

Page 20: ...F GB D I E...

Page 21: ...F GB D I E...

Page 22: ...F GB D I E 1918...

Page 23: ...F GB D I E...

Page 24: ...ioramento dei nostri prodotti ci riserviamo di modificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verb...

Reviews: