GB
15
1 Radiators zone
No.
Designation
Access
Range
Value / Default
Status:
01
Outside temperature
D
-40 / +90°C
Read only
02
Installation return water temperature
D
-40 / +90°C
03
(not used)
04
Water temperature resulting setpoint (installation return)
D
15 / 75°C
05
(not used)
06
(not used)
07
(not used)
08
Temperature ambiante zone 1
D
-40 / +90°C
09
(not used)
10
Generator control output status
D
0/1
11
(not used)
12
Boiler control output status (or ON/OFF valve opening)
D
0/1
13
On/Off valve closure control status
D
0/1
14
Circulating pump control output status
D
0/1
Air temperature settings:
20
Generator shut-down threshold (outside temperature)
T
-15/ +5°C
-5°C
21
Regional min. temperature (outside temperature)
T
-20 / +5°C
-7°C
22
Supplementary authorization threshold (outside temperature)
T
-5 / +20°C
5°C
23
No heating threshold (outside temperature)
T
10 / 25°C
17°C
24
Lowering of ECO temperature (ambiente)
T
1 / 6K
3K
25
Anti-freeze ambiance setpoint
T
8 / 18°C
12°C
Water temperature settings:
29
Water temperature setpoint in "anti-freeze" mode (return)
T
20 / 40°C
30°C
30
Heating water max. temperature (return)
T
25 / 60°C
50°C
31
(not used)
32
Heating water min. temperature (return)
T
17 / 40°C
20°C
33
(not used)
34
(not used)
35
(not used)
36
Thermodynamic heating authorization threshold (return)
T
10 / 20°C
15°C
37
(not used)
38
(not used)
39
(not used)
40
Supplementary triggering shift
T
1 / 10K
3K
Sensor:
50
Outside sensor
T
+ or -3K
0
51
Zone 1 ambient temperature sensor
T
+ or -3K
0
52
(not used)
53
Installation return water temperature sensor
T
+ or -3K
0
54
(not used)
55
(not used)
56
(not used)
57
(not used)
Miscellaneous and maintenance:
60
Default configuration
T
Init
61
TYPHONE language selection (1 = F ; 2 = GB)
T
1 / 2
1
62
TYPHONE access code
T
0 / 9999
1234
63
(not used)
64
Circulator control forcing
T
0 / 1
0
65
(not used)
66
(not used)
67
Generator control forcing
T
0 / 1
0
68
(not used)
69
Boiler control forcing
T
0 / 1
0