8.3 - FORCING OF CONTROL OUTPUTS

• Forcing: for maintenance operations only, when the system is "

OFF

", it is possible to force the control of the following outputs

by setting to parameter to "1":

- Parameter 64: circulating pump
- Parameter 67: generator
- Parameter 69: supplementary boiler

Caution: 
At the end of the operation, forcing must be deactivated (by returning the parameters "0") before
restarting the installation.

8.4 - GENERATOR LOAD SHEDDING

• This can be done:

- either by a potential-free contact,
- or from a "“Tele-Info” signal sent by the electrical utility meter (per specification EDF HN 44-S-81).

• Prohibits operation of the generator and the 2

nd

electric convector zone, if any.

• Signalled by icon on the display unit.

8.5 - 2

nd

ZONE - ELECTRIC CONVECTORS

• A 2

nd

zone equipped with electric convectors can also be managed (Max. number = 20). These appliances must be equipped

with an electronic thermostat (not included) able to receive signals via a 230 VAC pilot wire (standard GIFAM 4).

• The 2

nd

zone is activated by setting the microswitch in the back of the control unit to the "

ON

" position.

- In "

Comfort

", "

ECO

" or "

Anti-freeze

" heating modes, the corresponding signals are transmitted to the 2

nd

zone.

- In 

Off

position, the signal is transmitted to the 2

nd

zone.

- In 

heating mode with hourly programming

, the "

Comfort

" or "

ECO

" signals are transmitted to the 2

nd

zone according

to the corresponding hourly programming.

Note

In case of load shedding, a shut-down signal is transmitted to the 2

nd

zone.

- In heating mode, the display unit indicates for the zone 2 "

HEAT

.

8.6 - CIRCULATOR CONTROL

• In heating mode (

Comfort 

ECO

Anti-freeze

), the installation's circulating pump is actuated if the outside temperature is

below the non-heating threshold.

• Circulating pump shutdown is delayed 1 minute.
• A degripping device allows the circulating pump to start automatically, for 3 seconds every 24 hours, if it is off.
• The circulator must have its own thermal protection (not supplied). 

Note

:

The circulating pump built into the generator is factory-set to operate constantly as soon as generator power is on.
It is possible to operate this circulating pump only when the generator is controlled by this system.
To do this, on the generator's ECH regulator, change parameter H20 to “

4

” (see generator manual).

8.7 - PARAMETERS

Access:

- 2 access levels:

- Level 1, read only, with direct access for parameters 1 to 19,
- Level 2, ("technical level") accessible by password ("

see last page

").

This level is entered via parameter 20, although all parameters are accessible.

Procedure

:

1°)  Simultaneously press and hold the buttons 

and 

for 5 seconds, until

the screen displays 

PArA

.

2°) Select 

the 

User 

menu

= Level 1

or  

Installer = Level 2

using the 

and

buttons.

1: User
2: Installer

Summary of Contents for K 60 D 066 Z

Page 1: ...EGRAZIONE APPLICAZIONE 1 ZONA RADIATORI AZIONE TUTTO O NIENTE KIT DE REGULACI N PARA BOMBA DE CALOR CON CONEXI N DE CALDERA APLICACI N UNA ZONA RADIADORES ACCI N TODO O NADA SET STEUERMODUL UND SCHALT...

Page 2: ...aintenance of this kit must be performed by qualified and authorised personnel in accordance with current standards and recognized trade practices Before doing any work on the installation make sure i...

Page 3: ...cuit breaker 4 Terminal strip 5 Control board accessory location Bi PAC see specific installation manual 1 5 3 2 4 4 OPERATING PRINCIPLE The kit is designed allow complete installation control from th...

Page 4: ...coupling bottle Outside sensor 230 VAC power supply Installation according to current standards and recognised trade practices Dirt separator 70600114 Generator Note install the strainer filter suppli...

Page 5: ...l facing North North west and located away from parasitic heat sources chimney thermal bridge etc and sheltered from inclement weather under a roof overhand for example Connection as per paragraph 6 5...

Page 6: ...es do not route these cables near power cables A Generator load shedding signal if required Two possibilities 1 By a remote info signal coming from the electrical utility meter EDF French electrical u...

Page 7: ...d size 0 5 mm2 H Boiler supplementary valve control if any On Off control signal 230 V 50 Hz 30 VA maximum available on the box s terminal strip terminal 2 common connected to the Neutral terminal 1 v...

Page 8: ...ply 230 V 1 50 Hz Control unit Not used Water return temperature sensor Outside temperature sensor Printed Circuit Board Boiler authorisation Boiler fault contact unavailable as required Remove the br...

Page 9: ...e temperature and validation Liquid crystal display LCD Micro switch to activate a 2nd heating zone using electric convectors see paragraph 8 5 This micro switch is located on the back of the unit s p...

Page 10: ...ly Not used Boiler alarm input unavailable Not used Generator fault input Generator On Off output Generator H C output not used Outside temperature Installation return water temperature Potential free...

Page 11: ...int temperature of the zone adjustable from 15 to 25 C causes the resulting setpoint water temperature to decrease or increase of 2 degrees respectively However this variation cannot exceed 4 degrees...

Page 12: ...ope calculated according to the parameters of the control equipment is automatically corrected by the system by adding or subtracting a correcting coefficient the value of which is displayed in parame...

Page 13: ...ing mode with hourly programming the Comfort or ECO signals are transmitted to the 2nd zone according to the corresponding hourly programming Note In case of load shedding a shut down signal is transm...

Page 14: ...2 Go to parameter 70 Press the Z OK button the value of the parameter is displayed This value may be read or modified using the and buttons if the system is in the Stop position If parameters are modi...

Page 15: ...25 C 17 C 24 Lowering of ECO temperature ambiente T 1 6K 3K 25 Anti freeze ambiance setpoint T 8 18 C 12 C Water temperature settings 29 Water temperature setpoint in anti freeze mode return T 20 40...

Page 16: ...on the display Automatic reset the alarm disappears when the source of the fault is corrected Note The alarms are displayed even if the system is shutdown If several alarms occur simultaneously the v...

Page 17: ...lfunctions Ensure that the electric cables are properly protected from all sheet metal edges or metal parts that could damage them Ensure that control cables and power cables are properly separated Ch...

Page 18: ...hat all electrical connections are properly tight Check the ground connections Verification of the hydraulic circuit cleaning of the strainer filter and drip pan water quality purge pressure etc Verif...

Page 19: ...GB 19...

Page 20: ...F GB D I E...

Page 21: ...F GB D I E...

Page 22: ...F GB D I E 1918...

Page 23: ...F GB D I E...

Page 24: ...ioramento dei nostri prodotti ci riserviamo di modificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verb...

Reviews: