Technibel K 60 D 066 Z Installation Instruction Download Page 7

GB

7

B BUS

- 2-conductor cable, min. size 1 mm

2

.

-

Total

length of the BUS connection: 40 meters (heating board A1 / control box connection).

- To be connected to the heating board A1.

C Control box power supply

- 230 V, single-phase, 50 Hz + ground (Class I).

- It must be supplied from a protection and disconnect device in compliance with current regulations.
- Cable 3G 1.5 mm

2

.

- To be connected directly on circuit breaker 

Q1

of the box (Terminals 

U

and 

N

).

Note

: The control box is supplied by the BUS.

D Outside temperature sensor

- 2-conductor cable, min. size 0.5 mm

2

.

- Maximum length 25 meters.
- To be connected to the heating board A1.

E Generator control

- Shielded cable with 2 twisted pairs (shielding on generator side).

• 1 pair for generator on.
• 1 pair for the generator alarm signal.

- Min. cable size: 0.5 mm

2

.

- Maximum length 25 meters.
- To be connected to the heating board A1.

F Supplementary boiler authorisation

- Potential-free changeover contact, available on the box's terminal strip (terminals 

A

B

C

).

- 2 A resitive at 230 Vac maximum.
- Actuated contact = boiler authorised.
- This signal is not mandatory if the supplementary valve is connected.

G Boiler alarm unavailable (as required)

- A contact from the boiler can possibly be connected on the heating board A1 for signalling on the control box and closure

of the supplementary valve.

- This contact must be potential-free and of good quality.
- Contact open = alarm.
- A maximum connection length of 25 meters and size 0.5 mm

2

H Boiler supplementary valve control (if any)

- "On/Off" control signal, 230 V / 50 Hz (30 VA maximum) available on the box's terminal strip:

- terminal 2 = common (connected to the Neutral)
- terminal 1 = valve opening control
- terminal 3 = valve closing control

- It is possible to connect either a 3-point valve (3 wires) (available as an accessory), or a spring type return valve (2

wires).

- Minimum cable size 0.75 mm

2

.

J Circulator (if any)

- It is possible to supply a circulator with 230 V / 1 / 50 Hz directly via the box's terminal strip (Terminals 4 - Neutral / 5 -

Phase / Ground).

- Maximum current 1.6 A (for a superior current strength, the signal must be relayed).
- Cable 3G 1.5 mm

2

.

- The circulator must have its own thermal protection (not supplied).

L Water temperature sensor (installation return)

- Sensor delivered with a cable measuring 3.5m long. 
- This connection may be extended with a 2-conductor cable (minimum 0.5 mm

2

cross-section) and with a maximum

length of 25 meters.

- To be connected to the heating board A1.

X Pilot wire for electric convectors (if any)

- To send shut-down, "

Anti-freeze

" (prolonged absence) or "

Eco

" orders to electric convectors in zone 2. Convector

control (not supplied) must be adapted to receive this type of signal (standard GIFAM 4). Consult the manual of the
electric convectors.

- 230 VAC signal from the heating board A1.
- 1.5 mm

2

single-pole cable adapted for the operating voltage.

- Max. number of convectors controlled by the pilot wire: 20.
-

Note

: The electrical power supplied to the convectors must be the same as that of the control.

Note: ensure that the ground connections of the various system components are interconnected.

Summary of Contents for K 60 D 066 Z

Page 1: ...EGRAZIONE APPLICAZIONE 1 ZONA RADIATORI AZIONE TUTTO O NIENTE KIT DE REGULACI N PARA BOMBA DE CALOR CON CONEXI N DE CALDERA APLICACI N UNA ZONA RADIADORES ACCI N TODO O NADA SET STEUERMODUL UND SCHALT...

Page 2: ...aintenance of this kit must be performed by qualified and authorised personnel in accordance with current standards and recognized trade practices Before doing any work on the installation make sure i...

Page 3: ...cuit breaker 4 Terminal strip 5 Control board accessory location Bi PAC see specific installation manual 1 5 3 2 4 4 OPERATING PRINCIPLE The kit is designed allow complete installation control from th...

Page 4: ...coupling bottle Outside sensor 230 VAC power supply Installation according to current standards and recognised trade practices Dirt separator 70600114 Generator Note install the strainer filter suppli...

Page 5: ...l facing North North west and located away from parasitic heat sources chimney thermal bridge etc and sheltered from inclement weather under a roof overhand for example Connection as per paragraph 6 5...

Page 6: ...es do not route these cables near power cables A Generator load shedding signal if required Two possibilities 1 By a remote info signal coming from the electrical utility meter EDF French electrical u...

Page 7: ...d size 0 5 mm2 H Boiler supplementary valve control if any On Off control signal 230 V 50 Hz 30 VA maximum available on the box s terminal strip terminal 2 common connected to the Neutral terminal 1 v...

Page 8: ...ply 230 V 1 50 Hz Control unit Not used Water return temperature sensor Outside temperature sensor Printed Circuit Board Boiler authorisation Boiler fault contact unavailable as required Remove the br...

Page 9: ...e temperature and validation Liquid crystal display LCD Micro switch to activate a 2nd heating zone using electric convectors see paragraph 8 5 This micro switch is located on the back of the unit s p...

Page 10: ...ly Not used Boiler alarm input unavailable Not used Generator fault input Generator On Off output Generator H C output not used Outside temperature Installation return water temperature Potential free...

Page 11: ...int temperature of the zone adjustable from 15 to 25 C causes the resulting setpoint water temperature to decrease or increase of 2 degrees respectively However this variation cannot exceed 4 degrees...

Page 12: ...ope calculated according to the parameters of the control equipment is automatically corrected by the system by adding or subtracting a correcting coefficient the value of which is displayed in parame...

Page 13: ...ing mode with hourly programming the Comfort or ECO signals are transmitted to the 2nd zone according to the corresponding hourly programming Note In case of load shedding a shut down signal is transm...

Page 14: ...2 Go to parameter 70 Press the Z OK button the value of the parameter is displayed This value may be read or modified using the and buttons if the system is in the Stop position If parameters are modi...

Page 15: ...25 C 17 C 24 Lowering of ECO temperature ambiente T 1 6K 3K 25 Anti freeze ambiance setpoint T 8 18 C 12 C Water temperature settings 29 Water temperature setpoint in anti freeze mode return T 20 40...

Page 16: ...on the display Automatic reset the alarm disappears when the source of the fault is corrected Note The alarms are displayed even if the system is shutdown If several alarms occur simultaneously the v...

Page 17: ...lfunctions Ensure that the electric cables are properly protected from all sheet metal edges or metal parts that could damage them Ensure that control cables and power cables are properly separated Ch...

Page 18: ...hat all electrical connections are properly tight Check the ground connections Verification of the hydraulic circuit cleaning of the strainer filter and drip pan water quality purge pressure etc Verif...

Page 19: ...GB 19...

Page 20: ...F GB D I E...

Page 21: ...F GB D I E...

Page 22: ...F GB D I E 1918...

Page 23: ...F GB D I E...

Page 24: ...ioramento dei nostri prodotti ci riserviamo di modificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verb...

Reviews: