5.1 - CONTROL BOX INSTALLATION

• As the control unit is equipped with a temperature sensor, it must

be installed in a location that is representative of the temperature
of the comfort zone.

• Wall mounting: the unit must not be installed in corners, on

shelves or behind curtains, near sources or heat or directly
exposed to sunlight. The unit should be installed approximately
1.5 m above the floor.

• Open the box by removing the lower screw and secure the base

to the wall (mounting holes, item 

1

).

• Open the protective cover (screw 

2

) and connect the BUS link to

the control board (see chapter 6).

• Fit the control unit back on its base.

5.2 - INSTALLATION OF THE OUTSIDE TEMPERATURE SENSOR

• This sensor must be located outside in a location that is

representative of the temperature to be measured (on a wall
facing North/North-west) and located away from parasitic
heat sources (chimney, thermal bridge, etc..) and sheltered
from inclement weather (under a roof overhand, for
example).

• Connection as per paragraph 6.

5.3 - INSTALLATION OF THE WATER TEMPERATURE SENSOR

• To ensure proper operation:

- Ensure that the sensor is correctly secured to the piping. Use the metal retaining clamp supplied with this kit.
- Use thermoconductive paste to improve conductivity (not supplied).
- Insulate the assembly with insulating foam (not supplied).

5.4 - INSTALLATION OF THE ELECTRICAL CONTROL BOX

• To be installed in the equipment room (ambient temperature between 0 and 40°C).  IP 22,

once installed.

• Plastic wall-mounted control box.

- Install the mounting lugs, supplied with the kit, on the box.
- Secure the box to the wall using the screws / anchors supplied with the kit.

• Electrical connections: see paragraph 6.

Note

: The box must be supplied with 230 V / 1 / 50Hz.

1

2

Base

Rear view

5 - INSTALLATION

Mini 20 cm

1.50 m

Control unit

20 cm min.

244

244

Summary of Contents for K 60 D 066 Z

Page 1: ...EGRAZIONE APPLICAZIONE 1 ZONA RADIATORI AZIONE TUTTO O NIENTE KIT DE REGULACI N PARA BOMBA DE CALOR CON CONEXI N DE CALDERA APLICACI N UNA ZONA RADIADORES ACCI N TODO O NADA SET STEUERMODUL UND SCHALT...

Page 2: ...aintenance of this kit must be performed by qualified and authorised personnel in accordance with current standards and recognized trade practices Before doing any work on the installation make sure i...

Page 3: ...cuit breaker 4 Terminal strip 5 Control board accessory location Bi PAC see specific installation manual 1 5 3 2 4 4 OPERATING PRINCIPLE The kit is designed allow complete installation control from th...

Page 4: ...coupling bottle Outside sensor 230 VAC power supply Installation according to current standards and recognised trade practices Dirt separator 70600114 Generator Note install the strainer filter suppli...

Page 5: ...l facing North North west and located away from parasitic heat sources chimney thermal bridge etc and sheltered from inclement weather under a roof overhand for example Connection as per paragraph 6 5...

Page 6: ...es do not route these cables near power cables A Generator load shedding signal if required Two possibilities 1 By a remote info signal coming from the electrical utility meter EDF French electrical u...

Page 7: ...d size 0 5 mm2 H Boiler supplementary valve control if any On Off control signal 230 V 50 Hz 30 VA maximum available on the box s terminal strip terminal 2 common connected to the Neutral terminal 1 v...

Page 8: ...ply 230 V 1 50 Hz Control unit Not used Water return temperature sensor Outside temperature sensor Printed Circuit Board Boiler authorisation Boiler fault contact unavailable as required Remove the br...

Page 9: ...e temperature and validation Liquid crystal display LCD Micro switch to activate a 2nd heating zone using electric convectors see paragraph 8 5 This micro switch is located on the back of the unit s p...

Page 10: ...ly Not used Boiler alarm input unavailable Not used Generator fault input Generator On Off output Generator H C output not used Outside temperature Installation return water temperature Potential free...

Page 11: ...int temperature of the zone adjustable from 15 to 25 C causes the resulting setpoint water temperature to decrease or increase of 2 degrees respectively However this variation cannot exceed 4 degrees...

Page 12: ...ope calculated according to the parameters of the control equipment is automatically corrected by the system by adding or subtracting a correcting coefficient the value of which is displayed in parame...

Page 13: ...ing mode with hourly programming the Comfort or ECO signals are transmitted to the 2nd zone according to the corresponding hourly programming Note In case of load shedding a shut down signal is transm...

Page 14: ...2 Go to parameter 70 Press the Z OK button the value of the parameter is displayed This value may be read or modified using the and buttons if the system is in the Stop position If parameters are modi...

Page 15: ...25 C 17 C 24 Lowering of ECO temperature ambiente T 1 6K 3K 25 Anti freeze ambiance setpoint T 8 18 C 12 C Water temperature settings 29 Water temperature setpoint in anti freeze mode return T 20 40...

Page 16: ...on the display Automatic reset the alarm disappears when the source of the fault is corrected Note The alarms are displayed even if the system is shutdown If several alarms occur simultaneously the v...

Page 17: ...lfunctions Ensure that the electric cables are properly protected from all sheet metal edges or metal parts that could damage them Ensure that control cables and power cables are properly separated Ch...

Page 18: ...hat all electrical connections are properly tight Check the ground connections Verification of the hydraulic circuit cleaning of the strainer filter and drip pan water quality purge pressure etc Verif...

Page 19: ...GB 19...

Page 20: ...F GB D I E...

Page 21: ...F GB D I E...

Page 22: ...F GB D I E 1918...

Page 23: ...F GB D I E...

Page 24: ...ioramento dei nostri prodotti ci riserviamo di modificarli senza preaviso En el inter s de mejoras constantes nuestros productos pueden modificarse sin aviso pr vio Unsere Produkte werden laufend verb...

Reviews: