SYMBOL
MAX. ALLOWABLE
LIMIT OF TUBING
LIMIT OF ELEVATION
REQUIRED AMOUNT OF
OF INDOOR
TUBING LENGTH AT
LENGTH
DIFFERENCE
ADDITIONAL
UNIT
SHIPMENT
H
REFRIGERANT
(m)
(m)
(m)
(g / m)*
NARROW TUBE
LARGE TUBE
OUTER DIAMETER
MIN. THICKNESS
OUTER DIAMETER
MIN. THICKNESS
6,35 mm
0,8 mm
9,52 mm
0,8 mm
Cross section area (mm
2
)
4,0
1
1
–
Lenght (m)
20
20
20
25A
Power supply wiring
Power line
Control line
Delayed fuse
A
B
C
3
Installation site selection - Indoor unit
AVOID
• Direct sunlight.
• Nearby heat sources that may affect unit performance.
• Areas where leakage of flammable gas may be expected.
• Locations where large amounts of oil mist may occur (such as
in kitchen or near factory equipment) because oil contamination
can cause operation problems and may deform plastic surfaces
and parts of the unit.
• Unsteady locations that will cause noise or possible water
leakage.
• Locations where the remote control unit will be splashed with
water or affected by dampness or humidity.
• To make holes in areas where electrical wiring or conduits are
located.
DO
• Select an appropriate position from which every corner of the
room can be uniformily cooled.
• Select a sufficiently strong location to support the weight of the
unit.
• Select a location where tubing and drain hose have the shortest
run to the outside.
• Allow acces for operation and maintenance as well as
unrestricted air flow around the unit.
Installation site selection - Outdoor unit
AVOID
• Heat sources, exhaust fans.
• Direct sunlight.
• Damp, humid or uneven locations.
• To make holes in areas where electrical wiring or conduits are
located.
DO
• Choose places as cool as possible and well ventilated.
• use lug bolts or equal to bolt down the unit, reducing vibration
and noise.
ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)
●
Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with foamed polyethylene
(min. thickness 8mm).
●
PVC pipe for condensate drain pipe (ø int.18mm) in length suitable to connect the condensation to the outside drainage.
●
Anti-freeze oil for flare connections (about 30g.).
●
Electric wire: use insulated copper wires of size and length as shown at paragraph “SYSTEM WIRING DIAGRAMS”
ELECTRICAL DATA
LENGTH, SIZE WIRES AND DELAYED FUSE
TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
LA1+LA2
15 (LA1 o LA2 > 2m)
30 (LA1 o LA2 < 15m)
7
15
LB1+LB2
15 (LA1 o LA2 > 2m)
30 (LA1 o LA2 < 15m)
* If total tubing length (LA1 + LA2 o LB1 + LB2) becomes 15m to 30m (max.), charge additional refrigerant by 15g/m.
No additional charge of compressor oil is necessary.
(go on page 4)
EG