IMPORTANT!
Please read before installation

This air conditioning system meets strict safety and operating
standards.
For the installer or service person, it is important  to install or
service the system so that it operates safely and efficiently.

For safe installation and trouble-free operation, you must:
• Carefully read this instruction booklet before beginning.
• Follow each installation or repair step exactly as shown.
• Observe all local, state and national electrical  codes.
• Pay close attention to all warning and caution notices given in

this manual.

•The unit must be supplied with a dedicated electrical line.

This symbol refers to a hazard or unsafe practice which can result
in severe personal injury or death.

This symbol refers to a hazard or unsafe practice which can result
in personal injury or product or property damage.

If necessary, get help
These instructions are all you need for most installation sites and
maintenance conditions.
If you require help for a special problem, contact our sale/service
outlet or your certified dealer for additional instructions.

In case of improper installation
The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow the
instructions in this document.

SPECIAL PRECAUTIONS

• During installation, connect before the refrigerant system

and then the wiring one; proceed in the reverse orden when
removing the units.

When wiring

ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A QUALIFIED,
EXPERIENCED ELECTRICIANS SHOULD ATTEMPT
TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubing are

completed or reconnected and checked, to ensure the grounding.

• Highly dangerous electrical voltages are used in this system.

Carefully refer to the wiring diagram and these instructions when
wiring.
Improper connections and inadequate grounding can cause
accidental injury and death.

• Ground the unit following local electrical codes.
• The Yellow/Green wire cannot be used for any connection

different from the ground connection.

• Connect all wiring tightly. Loose wiring may cause overheating

at connection points and a possible fire hazard.

• Do not allow wiring to touch the refrigerant tubing, compressor,

or any moving parts of the fan.

• Do not use multi-core cable when wiring the power supply and

control lines. Use separate cables for each type of line.

When transporting
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminium fins on
the air conditioner can cut your fingers.

When installing...
... In a ceiling or wall
Make sure the ceiling/wall is strong enough to hold the unit-weight.
It may be necessary to build a strong wooden or metal frame to
provide added support.

... In a room
Properly insulate any tubing run inside a room to prevent
"sweating", which can cause dripping and water damage to walls
and floors.

... In moist or uneven locations
Use a raised concrete base to provide a solid level foundation for
the outdoor unit.
This prevents damage and abnormal vibrations.

... In area with strong winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.

... In a snowy area (for heat pump-type systems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.

When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare

and union tubes before connecting them;  screw by hand and
then tighten the nut with a torque wrench for a leak-free
connection.

• Check carefully for leaks before starting the test run.

NOTE:
Depending on the system type, liquid and gas lines may be either
narrow or wide. Therefore, to avoid confusion, the refrigerant
tubing for your particular model is specified as narrow tube for
liquid, wide tube for gas.

When servicing
• Turn the power OFF at the main power board  before opening

the unit to check or repair electrical parts and wiring.

• Keep your fingers and clothing away from any moving parts.
• Clean up the site after the work, remembering to check that no

metal scraps or bits of wiring have been left inside the unit being
serviced.

• Ventilate the room during the installation or testng the refrigeration

system; make sure that, after the installation, no gas leaks are
present, because this could produce toxic gas and dangerous
if in contact with flames or heat-sources.

WARNING

CAUTION

WARNING

Summary of Contents for GR360M4R5TAA

Page 1: ...27 C D B Heating Minimum conditions Outdoor temperature 5 C D B 6 C W B ACCESSORIES SUPPLIED WITH THE UNIT EG I F E P GR Model Combinations 4 units Combine indoor and out door units only as listed bel...

Page 2: ...wiring to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line W...

Page 3: ...the weight of the unit Select a location where tubing and drain hose have the shortest run to the outside Allow acces for operation and maintenance as well as unrestricted air flow around the unit In...

Page 4: ...ture interna 27 C B S Condizioni Minime in Riscaldamento Temperatura esterna 5 C B S 6 C B U MATERIALE DI CORREDO I PARTI FIGURA Q T PARTI FIGURA Q T TASSELLO 6 VITE 6 AUTOFILETTANTE TELECOMANDO 1 AAA...

Page 5: ...o con i tubi refrigeranti il compressore o le parti mobili del ventilatore Nel collegare l alimentazione e le linee di controllo non usare cavi a pi conduttori Usare cavi separati per ciascun tipo di...

Page 6: ...rti elettriche o impianti PREFERIBILE Scegliere aree possibilmente in ombra e leggermente ventilate Fissare l unit alla base di appoggio per evitare vibrazioni MATERIALE ADDIZIONALE PER L INSTALLAZION...

Page 7: ...24 C B S 18 C B H Temp rature interi ure 27 C B S Conditions minimales en Chauffage Temp rature ext rieure 5 C B S 6 C B H GF ACCESSOIRES LIVRES AVEC L UNITE Outillage necessaire l installation non l...

Page 8: ...incendie Il ne faut en aucun cas laisser les c bles toucher la tuyauterie du r frig rant le compresseur ou toute pi ce mobile N utilisez pas de c ble multiconducteur pour le c blage des lignes d alime...

Page 9: ...trous o il y a des c bles lectriques ou des conduits RECHERCHEZ Un emplacement aussi frais que possible et bien ventil Utilisez des boulons ou similaire pour fixer l appareil afin d en r duire le bru...

Page 10: ...iones M nimas en Calefacci n Temperatura exterior 5 C B S 6 C B H MATERIAL SUMINISTRADO GE Material necesario para la instalaci n no suministrado 11 Destornillador de cabeza plana 12 Destornillador me...

Page 11: ...n contacte con el tubo de refrigerante compresor o parte m viles del ventilador No use cable coaxial para cablear las l neas de potencia y las de control Use cables separados para cada una de las l n...

Page 12: ...legir zonas a la sombra ligeramente aireadas Fijar la unidad a la base de apoyo para evitar vibraciones DATOS ELECTRICOS LONGITUD SECCION DE CABLES Y FUSIBLES DE ACCION RETARDADA LIMITES LONGITUD DE L...

Page 13: ...5 C B S 6 C B H INSTRU ES DE INSTALA O Sistema de ar condicionado de Unidades Separadas ACESS RIOS FORNECIDOS COM A UNIDADE PE AS FIGURA Q DE PE AS FIGURA Q DE BUCHA DE FIXA O 6 RAWPLUG PARAFUSOS DE A...

Page 14: ...bagem de refrigera o no compressor ou em quaisquer pe as m veis da ventoinha N o use fios de v rios n cleos ao fazer a instala o el trica e as linhas de controle Use fios separados para cada tipo de l...

Page 15: ...o Local de Instala o da Unidade para Montagem no Exterior EVITE Fontes de calor ventoinhas de escape de ar quente A luz direta do sol Locais h midos ou irregulares De perfurar zonas onde est o dispost...

Page 16: ...vsei Qevrmansh Exwterikhv qermokrasiva 5 C B S 6 C B U GR DIAQESIMA BOHQHTIKA EXARTHMATA Aparaivthta ergaleiva gia thn egkatavstash den promhqeuvontai 11 Katsabivdi stavntar 12 Staurokatsavbidomesaivo...

Page 17: ...prevpei na evrqoun se epafhv me tou swlhvne yuvxh to susmpiesthv hv ta kinhtav tmhvmata tou anemisthvra Katav th suvndesh th trofodosiva kai twn grammwvn elevgcou mh crhsimopoieivtai kalwvdia me peri...

Page 18: ...natovn cwvrou se skiav kai exaerizovmenou Staqeropoihvste th monavda sth bavsh sthvrixh gia na apofuvgete tou kradasmouv SUMPLHRWMATIKO ULIKO GIA THN EGKATASTASH DEN PROMHQEUEAI Yuktikov swlhvna apoxe...

Page 19: ...shmeiva pou shmadeuvontai me evna trivgwno kai xegantzwvsete ta duvo plastikav tou kapakiouv The unit can be connected to five directions right rear left rear right side left side and right downward L...

Page 20: ...uche des tubes utiliser le marquage le plus ext rieur du panneau Para la salida de los tubos del lado izquierdo de la parte posterior utilizar las marcas exteriores del panel Para a sa da da tubagem t...

Page 21: ...n haut Desenganchar el panel frontal con un destornillador por los tres puntos marcados Coger el panel con las manos y sacarlo desliz ndolo hacia arriba Extraia o painel frontal com uma chave de paraf...

Page 22: ...mplokarivsmato kai efarmovste elafrav pivesh sta shmeiva autav I EG F E P GR N The refrigerant tubes and drain hose are on the right side of the unit The drain tray is supplied with two outlets with...

Page 23: ...g power wires plus earth wire from indoor to outdoor unit see tab for size of wires Stendere un cavo multipolare con filo di terra tra le due unit vedere tabella per la sezione dei fili Passer les fil...

Page 24: ...ento dall esterno quindi piegarle verso destra rimuovere la parte inferiore amovibile della struttura Appendere l unit ed estendere il supporto posteriore per facilitare il lavoro di collegamento SORT...

Page 25: ...de la regleta de bornes problemas de funcionamiento del acondicionador de aire con peligro de incendio Predisponha os fios para conex o com a placa de terminais Ligue e fixe cada fio ao pr prio termin...

Page 26: ...etto scarico della condensa e rimontare la griglia come al punto L Remplir le bac et v rifier que la sortie des condensats soit correcte Remonter la grille selon L Llenar el tubo y controlar que el l...

Page 27: ...ised from the ground level Fix unit to base using 4 anchor bolts Predisporre l unit esterna su base solida rialzata dal terreno e fissarla con 4 bulloni ad espansione Mettre l unit ext rieure sur une...

Page 28: ...racter sticas superficie interior lisa y pulida borde exterior uniforme y liso tavellanadura c nica de longitud uniforme Lubricar con aceite anticongelante las superficies de contacto luego atornillar...

Page 29: ...o teste de fugas Monwvste prosektikav tou swlhvne afhvnwnta ti enwvsei akavlupte gia na givnei o scetikov evlegco diarrohv L I EG F P The service port on the wide tubes service valves uses a Schrader...

Page 30: ...en el circuito frigor fico pueden provocar da os al sistema Conectar la bomba de vac o a la v lvula de baja presi n del circuito B1 Poner en marcha la bomba de vac o el tiempo aconsejado en la tabla...

Page 31: ...iorario Rimontare i cappucci ed il bocchettoni stringere con momento torcente di 200 kg cm Ouvrir compl tement les vannes de service dans le sens contraire aux aiguilles d une montre Monter nouveau le...

Page 32: ...nipolare di disinserzione dalla rete interruttore generale deve essere del tipo adatto con distanza minima di apertura dei contatti di 3 mm Le dispositif omnipolaire de protection et de sectionnement...

Page 33: ...C ble lectrique multipolaire la section et la longueur du c ble lectrique recommand sont indiqu es dans le tableau Donn es lectriques Le c ble doit tre de type H07RN F selon CEI 20 19 CENELEC HD22 As...

Page 34: ...C sem liga o terra A sec o e o comprimento do cabo el ctrico recomendado consta do cap tulo Caracter sticas El ctricas O cabo dever ser do tipo A07RN F pelo menos de acordo com CEI 20 19 CENELEC HD22...

Page 35: ...jado hasta un valor que va de 1 a 0 5 Kg cm2 cerrar completamente la v lvula de baja presi n del circuito B2 y luego la del circuito B1 Apagar el acondicionador Ative o aparelho de ar condicionado na...

Page 36: ...rant system Therefore be sure to use a hose connector which has a push pin inside La valvola di servizio dei rubinetti dell unit esterna da utilizzare per il vuoto del sistema ripristino carica refrig...

Page 37: ...figure et appuyer le bouton avec une plume Le climatiseur change mode de fonctionnement de OFF en Mode de Refroidissement en Mode de Chauffage chaque foi le bouton est appuy Para utilizar el acondici...

Page 38: ...DA ELETTRICA CARTE ELECTRONIQUE STEUERGER T CONTROLADOR PAINEL EL TRICO ELEGKTHS PR POWER RELAY REL ALIMENTAZIONE RELAIS D ALIMENTATION LEISTUNGSRELAIS REL DE ALIMENTACI N REL DAALIMENTA AO RELE ISCUO...

Reviews: