TDK-Lambda PH Series Manual Download Page 55

PH

300S, 600S

PH

B-353

・All specifications are subject to change without notice.

PC

It is control terminal for parallel operation. It is connected 
in all of PH modules in parallel operation. Shorten a wire 
between PC terminals as much as possible. Unavoidably 
the wire is long, then use twisted pair wire or shielded wire 
to avoid noise affects.
When PC terminals in parallel operation are mutually con-
nected,  voltage  of  all  PC  terminal  is  the  average  of  PC 
terminals at open circuit. +Input side of internal Op-Amp 
A1(2/2)  of  parallel  operation  in  proportion  to  the  output 
current in the module is supplied. At -input, voltage in pro-
portion to average of total output currents of all the mod-
ule is supplied. This Op-Amp makes output voltage of PH 
modeles  with  less  output  current  risen  by  TRM  terminal 
and activates output current in PH module balance.

TRM

TRM  terminal  in  each  PH  module  is  connected.  Con-
necting TRM terminal, control circuit of parallel operation 
adjusts the output voltage of the module and balance the 
output current.

-S

It is GND level of control circuit of parallel operation. Inter-
nal circuit activates based on -S. It shall be connected to 
-S terminal of PH module. -S connection between modules 
is to be connected one point of earth to avoid electrical 
potential difference of each -S terminal of PH module by 
voltage drop due to output current.

(3)Component Selection

Refer to following items to select components in control 
circuit of parallel operation

Op-Amp (A1)

Use an Op-Amp which has singular power operation and 
its  input  common  mode  voltage  range  from  0V.  More-
over, it shall be low input off set voltage. For an example, 
uPC842C(NEC) is one of available Op-Amp.

Transistor・FET (Q1-Q3)

FET (Q1) uses as analog switch. Use N channel small sig-
nal MOS-FET for general purpose (rated more than 25V, 
50mA.) 
Use  NPN  small  signal  type  for  transistor  (Q2-Q4)  (rated 
more than 25V, 50mA.)

Capacitor (C1-C6)

For choosing capacitor(s), refer to values expressed in Fig-
ure3-2 and values for each component shown in Table3-2. 
Use film capacitor or ceramic capacitor which has good 
temperature characteristics. 
The tolerance shall be less than ±5% .

Resistor (R1-R23, VR1)

For choosing capacitor(s), refer to values expressed in Fig-
ure3-2 and values for each component shown in Table3-2. 
The tolerance shall be less than ±5% .

Values for each Component

Values of Capacitor C1, Resistor R1-R4, R18, R20, R23, 
and Variable Resistor VR1 depend on model. Refer to Ta-
ble3-1 for components in PH300S280-*and Table3-2 for 
components in PH600S280-*.

PH300S280, PH30048

C1
R1
R2
R3
R4
R18
R20
R23
VR1

  3.3V 

5V 

12V 

15V 

24V 

28V 

48V

 1000p  1000p  1000p  330p  330p  1000p  330p
  1.2k 

1.2k 

1.2k 

2.7k 

5.1k 

7.5k 

10k

  1.2k 

1.2k 

1.2k 

2.7k 

5.1k 

7.5k 

10k

  150k  150k  300k  430k  750k  470k 

750k

  180k  180k  360k  470k  820k  510k 

820k

  9.1k 

30k 

30k 

30k 

30k 

30k 

30k

  5.6k 

12k 

15k 

15k 

15k 

15k 

15k

  18k 

18k 

11k 

4.7k 

2.4k 

1.8k 

360k

  50k 

50k  100k  100k  200k  100k 

200k

Table3-1 PH300S280, PH300S48

Values for components in Control 
Circuit of Parallel Operation

PH600S280

C1
R1
R2
R3
R4
R18
R20
R23
VR1

  3.3V 

5V 

12V 

15V 

24V 

28V 

48V

 1000p  1000p  1000p  330p  330p  1000p  1000p
  1.2k 

1.2k 

1.2k 

2.7k 

5.1k 

7.5k 

10k

  1.2k 

1.2k 

1.2k 

2.7k 

5.1k 

7.5k 

10k

  180k  180k  220k  360k  510k  200k 

390k

  200k  200k  270k  390k  560k  240k 

430k

  9.1k 

30k 

30k 

30k 

30k 

30k 

30k

  5.6k 

12k 

15k 

15k 

15k 

15k 

15k

  18k 

18k 

11k 

4.7k 

2.4k 

1.8k 

360k

  50k 

50k  100k  100k  200k  100k 

100k

Table 3-2  PH600S280

Values for components in Control 
Circuit of Parallel Operation

unit : C[F], R[Ω]

Others

Values of capacitors and resistors are recommended val-
ues  to  operate  power  modules  which  have  components 
used in basic connection shown in Application Note. These 
values may sometimes differ from the optimum values be-
cause of components at input and output side and wiring 
environment. Confirm the performance of the circuit using 
actual module when each value is determined.

4 Cautions for Wiring

Wiring from Input of A1 (1/2) to CS and -V terminals shall 
be minimum length. Be aware of noise affects for A1 (1/2) 
which makes small voltage amplify tens to hundreds times.
Also, load wire to united point of each load wire from output 
of the power supply shall be minimum length too. Long wir-
ing can cause mis-operation of control circuit of parallel op-
eration. Unavoidably the wire is long, then attach an approx. 
1mF capacitor between -V terminal and -S terminal. 
If -S wiring is close by and parallel to load wire, use shield-
ed wire or twisted pair wire to connect -S to -V and also -S 
itself. Without any measure, electrode of -S may be unstable 
by influences of load wire and mis-operation may be oc-
curred.

Summary of Contents for PH Series

Page 1: ...peration Current sharing load current balance IOG inverter operation monitoring signal AUX AUX BIAS power output Internal capacitor PH50 150 300F Aluminum electrolytic output smooth ing ceramic PH300S...

Page 2: ...F Model S Output Current Model F 2V 15A PH75F110 2 30A PH150F110 2 60A PH300F110 2 3V 15A PH75F110 3 30A PH150F110 3 60A PH300F110 3 3 3V 5V 10A PH50S110 5 15A PH75F110 5 PH75S110 5 30A PH150F110 5 PH...

Page 3: ...ad Regulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100 150 240 280 Voltage Adjustable Range 8 10 10 At 24VDC input Function Over Current Protection 4 105 15...

Page 4: ...rating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1h each Shock 196 1m s In pac...

Page 5: ...8 112 Maximum Load Regulation 3 mV 96 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 150 280 Voltage Adjustable Range 10 20 60 Function Over Current Protection 4 105 140 Over Voltage Pr...

Page 6: ...e Environment Operating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration 0...

Page 7: ...ating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10...

Page 8: ...75 6 75 76 8 75 6 Voltage Setting Accuracy 1 1 Maximum Line Regulation 2 mV 20 48 60 96 112 Maximum Load Regulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100...

Page 9: ...ronment Operating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no o...

Page 10: ...erating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 1...

Page 11: ...sible Open collector output Environment Operating Temperature 6 20 to 85 Baseplate Ambient temperature MIN 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10...

Page 12: ...ating Temperature 6 20 to 100 Baseplate Ambient temperature min 20 20 to 100 100 20 to 90 100 100 83 Storage Temperature 40 to 100 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No d...

Page 13: ...en collector output Environment Operating Temperature 6 20 to 85 Baseplate Ambient temperature MIN 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No d...

Page 14: ...midity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1 h each Shock 196 1m s In package Coo...

Page 15: ...ating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1h each Shock 196 1m s In pack...

Page 16: ...gulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100 150 240 280 Voltage Adjustable Range 10 20 20 60 Function Over Current Protection 4 105 140 Over Voltage P...

Page 17: ...wdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1 h each Shock 196 1m s In package Cooling 7 Conduction cooled Isolation Withstand Voltage Input...

Page 18: ...0 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X...

Page 19: ...ting Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1h each Shock 196 1m s In packa...

Page 20: ...50 4 Voltage Setting Accuracy 1 1 Maximum Line Regulation 2 mV 20 48 60 96 112 Maximum Load Regulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100 150 240 280...

Page 21: ...ting Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 5...

Page 22: ...ltage Setting Accuracy 1 1 Maximum Line Regulation 2 mV 20 48 60 96 112 Maximum Load Regulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100 150 240 280 Voltage...

Page 23: ...Environment Operating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At...

Page 24: ...o dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz amplitude sweep for 1min 0 825mm constant maximum 49 0m s X Y Z 1h each Shock 196 1m s In package Cooling 7 Conduction...

Page 25: ...W 60 90 150 151 2 Voltage Setting Accuracy 1 1 Maximum Line Regulation 2 mV 20 48 60 96 112 Maximum Load Regulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100...

Page 26: ...30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1h each Shock 196 1m s Cooling 7 Conduction coo...

Page 27: ...tput Environment Operating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibratio...

Page 28: ...ure 6 20 to 100 Baseplate Ambient temperature min 20 20 to 85 100 100 80 Storage Temperature 40 to 100 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no opera...

Page 29: ...er chassis mounting FG Screws must not pro trude into power module by more than 12 7mm Back side for heat sink C Input and output terminal 4 2 8 0 6 PH100S Packege Type T62 See note B See note C See n...

Page 30: ...are shown here in accordance with the specifications B M3 tapped holes 4 for customer chassis mounting FG Screws must not protrude into power module by more than 12 7mm Back side for heat sink C Inpu...

Page 31: ...country of manufacture and safety marking UL C UL BSI CE marking are shown here in accordance with the specifications B M3 tapped holes 4 for customer chassis mounting FG C Input and output terminal 6...

Page 32: ...en input interruption is less than 1s for PH50S 75S 100S and 150S series In case of input interruption please use F type PHs Sequence Time Chart PH50S 75S 100S 150S 300S 600S OVP Trip INPUT ON INPUT O...

Page 33: ...ence Time Chart PH75F 100F 150F 300F Input Voltage Output Voltage L L L IOG H H H L H L H 1 ON OFF Control 1 Level 4 H 35 V or Open 0 L 0 8 V or Short 2 7 10 VDC 2 AUX OCP Set Point INPUT ON REMOTE OF...

Page 34: ...en the unit is operating keep your hands and face away from the unit You may get injured by an accident Caution Confirm that connections to input output terminals and signal terminals are correct as i...

Page 35: ...ow ESR type Nippon Chemi con capacitors or equivalent are recommended For 24V input use LXY Series For 48V input use LXV Series For 110V and 280V input use KMG Series L1 To reduce ripple current at C1...

Page 36: ...g the external trimmer variable resis tor However note that OVP Over Voltage Protection will be activated when the output voltage is raised over specifi cation range Furthermore when the output voltag...

Page 37: ...ted within 60 20 2V 3V 20 of nominal voltage range However note that OVP will be activated when output voltage is raised over specification range Furthermore when the output voltage is adjusted to hig...

Page 38: ...TRM VR Load R1 Figure2 7 Connection Example of External Resistor In the same way remote sensing wires can be connected to load terminal input Changing Output Voltage by Applying External Reference Vol...

Page 39: ...C Input 25VDC 10VDC 280VDC Input 90VDC 25VDC Table7 1 Input Voltage to Release OVP 8 THERMAL PROTECTION Thermal protection is provided This function activates for abnormal ambient temperature rise and...

Page 40: ...each module should not exceed specifications By setting accuracy of output voltage of each power mod ule in parallel operation within 1 the maximum load current can be used up to 95 of nominal output...

Page 41: ...seplate temperature below 85 at actual operating conditions operation is possible For details of thermal design refer to Application Note Thermal Design OPERATING HUMIDITY Note that dew condensations...

Page 42: ...ut and baseplate at 500VDC Figure22 1 Insulation Test VIBRATION Refer to Application Note Installation Power Module Vibration specification value is the value when Power Module alone is mounted on Pri...

Page 43: ...h a common mode choke coil at input of each power module Accuracy of output voltage adjustment shall be within 1 The maximum load current shall be less than 95 of nomi nal output current Ground of PC...

Page 44: ...s damaged or failed 1 No Output Is the rated input voltage supplied Are the ON OFF control terminal remote sensing terminal and output volatage trimming terminal con nected correctly For adjusted outp...

Page 45: ...nsidered as an energy hazard 240VA power and 2V voltage and must not be accessible to a user End equipment manufacturers must provide protection against inadvertent contact with the output terminal on...

Page 46: ...o en sure the safety operation and to acquire safety standard approvals attach an external fuse The external fuse must be fast blow type and be attached to each module indi vidually Furthermore attach...

Page 47: ...o Vo 3 3V 5V 12V 15V 24V 28V 48V 300S 600S 6 3V 6 3V 4700 F 10000 F 10V 10V 3900 F 4700 F 25V 25V 1000 F 2200 F 25V 25V 1000 F 2200 F 35V 35V 560 F 1000 F 50V 50V 470 F 820 F 50V 50V 1 470 F 2 1 680 F...

Page 48: ...V 48V Output 12V 15V 24V 48V Output 12V 15V 24V 48V Output 3 3V 5V 48V Output 3 3V 5V 48V Output 12V 15V 24V 48V Output 12V 15V 24V 48V Output 36 Figure2 1 Limit of Input Voltage Connection method of...

Page 49: ...than 100ms To check OVP function apply an external voltage that is limited to upper limit of maximum OVP range Refer to specification for OVP range Avoid to apply over voltage not to damage the unit I...

Page 50: ...void such a damage ensure all the terminals are con nected before input is applied CS Signal CS Negative voltage based on Vo is generated for CS termi nal Using this signal it is possible to operate i...

Page 51: ...y condi tions it makes each terminal oxidize Hence the quality of the soldering would be worse Cooling Method Various cooling method can be used since the operating temperature is specified by basepla...

Page 52: ...onfirm its performance For details please refer Power Module Appli cation Note Please refer to Power Module Application Note for thermal design and mounting direction Confirm the following items befor...

Page 53: ...e load currents 2 PRECUATIONS There are several basic cautions and warnings in parallel operation of PH300S 600S series Externally attach a control circuit of parallel operation in each power module A...

Page 54: ...sistance rate of copper and approximately 4000 ppm For CS terminal voltage is a small voltage in negative polarity Op Amp A1 1 2 is amplifier inverting shown as Figure3 2 For all of PH modules to be i...

Page 55: ...refer to values expressed in Fig ure3 2 and values for each component shown in Table3 2 The tolerance shall be less than 5 Values for each Component Values of Capacitor C1 Resistor R1 R4 R18 R20 R23...

Page 56: ...output voltage Control Circuit of Parallel Operation Control Circuit of Parallel Operation Load Figure5 2 Parallel Operation at programmed ouput voltage c Parallel Operation with adjustable output vo...

Page 57: ...ange Control Circuit of Parallel Operation Control Circuit of Parallel Operation Load Figure6 2 N 1 Redundant Operation at programmed output voltage fixed c N 1 Redundant Operation with adjustable out...

Page 58: ...B 356...

Reviews: