TDK-Lambda PH Series Manual Download Page 39

PH

50 

150, 75 

300F

PH

B-337

・All specifications are subject to change without notice.

+V

−V

50mm

Load

Oscilloscope

JEITA

Attachment

   R:50Ω

   C:4700pF

As Short as Possible

1.5m  50Ω

Coaxial Cable

 Figure3-1: Measurement Method of Maximum Output 

Ripple Voltage 

(including Noise)

4 MAXIMUM LINE REGULATION

Maximum line regulation is defined as the output voltage 
deviation when the input voltage is slowly varied (steady-
state) within the input voltage range.

5 MAXIMUM LOAD REGULATION

Maximum load regulation is defined as the output voltage 
deviation when the output current is slowly varied (steady-
state) within the output current range.

〈S type〉

A minimum load current of more than 3% (4% for PH50S) 
of the nominal output current shall be taken  when the load 
current is dynamically changed. In case the load current is 
changed from less than the above minimum load current 
value, the output voltage may dynamically fluctuate. 
When using module in dynamic load mode, audible noise 
could be heard and output voltage fluctuation will increase. 
Therefore,  please  evaluate  thoroughly  when  using  this 
module.

6 OVER CURRENT PROTECTION (OCP)

OCP function is provided.
Output will automatically recover when short or overload 
condition is released. This setting value is fixed and can-
not be change externally.
Note that the module may be damaged depending on ther-
mal conditions when operating continuously under short or 
overload condition for a long period. 

7 OVER VOLTAGE PROTECTION (OVP)

OVP function is provided.
The setting value is relative to the nominal output voltage 
and is fixed. Therefore, it cannot be changed externally.
To recover the output voltage after OVP function activates, 
wait until input voltage becomes less than the following 
voltage values and then reapply input voltage.

 S type

F type

  24VDC Input

10VDC

10VDC

  48VDC Input

13.5VDC

4.5VDC

110VDC Input

25VDC

10VDC

280VDC Input

90VDC

25VDC

Table7-1: Input Voltage to Release OVP

8 THERMAL PROTECTION

Thermal protection is provided.
This function activates for abnormal ambient temperature 
rise and abnormal internal temperature rise of power supply 
and shuts the output off. Thermal protection will activate at 
100±15℃ baseplate temperature.
To recover the output, shut off the input once, and then 
reapply  input  after  the  baseplate  temperature  has  been 
cooled down sufficiently.

9 REMOTE SENSING (+S, -S TERMINALS)

In  the  power  modules  except  S  type  of  50W  and  75W, 
there are remote sensing terminals to compensate the volt-
age drop caused by wiring to load terminal from output ter-
minal of the power supply. If the remote sensing function is 
unnecessary (i.e. local sensing is used), shorten with wires 
+S terminal to +V terminal, and -S terminal to -V terminal.
Compensated voltage range of line drop (voltage drop by 
wiring) shall be set such that output voltage bV 
and –V does not exceed specified output voltage range and 
output must be within the maximum output power value. 
Also, line drop voltage between -V and -S (-V and negative 
side of the load) shall be less than 2V. To avoid and to 
decrease the noise affects, shielded wire, twisted wire, and 
parallel pattern wire etc. shall be used as remote sensing 
wire.

+V

+S

−V

−S

Load

Stabilize the output voltage at

Load terminal

+V

+S

−V

−S

Load

Stabilize the output voltage at

output terminal

Figure9-1: Using Remote Sensing

+V

+S

−V

−S

Load

Stabilize the output voltage at

Load terminal

+V

+S

−V

−S

Load

Stabilize the output voltage at

output terminal

Figure9-2: Without Remote Sensing

 ON/OFF CONTROL (CNT TERMINAL)

The output can be turned on or off without shutting down 
the input.
The control circuit is in the input side (primary side), and 
CNT terminal is used. The ground of CNT terminal is SG 
terminal for a module with SG terminal, and -V

in

 terminal 

for a module without SG terminal. -V terminal and SG ter-
minal is connected inside of the module. If this function is 
unnecessary, short CNT and SG terminals. 

Summary of Contents for PH Series

Page 1: ...peration Current sharing load current balance IOG inverter operation monitoring signal AUX AUX BIAS power output Internal capacitor PH50 150 300F Aluminum electrolytic output smooth ing ceramic PH300S...

Page 2: ...F Model S Output Current Model F 2V 15A PH75F110 2 30A PH150F110 2 60A PH300F110 2 3V 15A PH75F110 3 30A PH150F110 3 60A PH300F110 3 3 3V 5V 10A PH50S110 5 15A PH75F110 5 PH75S110 5 30A PH150F110 5 PH...

Page 3: ...ad Regulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100 150 240 280 Voltage Adjustable Range 8 10 10 At 24VDC input Function Over Current Protection 4 105 15...

Page 4: ...rating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1h each Shock 196 1m s In pac...

Page 5: ...8 112 Maximum Load Regulation 3 mV 96 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 150 280 Voltage Adjustable Range 10 20 60 Function Over Current Protection 4 105 140 Over Voltage Pr...

Page 6: ...e Environment Operating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration 0...

Page 7: ...ating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10...

Page 8: ...75 6 75 76 8 75 6 Voltage Setting Accuracy 1 1 Maximum Line Regulation 2 mV 20 48 60 96 112 Maximum Load Regulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100...

Page 9: ...ronment Operating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no o...

Page 10: ...erating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 1...

Page 11: ...sible Open collector output Environment Operating Temperature 6 20 to 85 Baseplate Ambient temperature MIN 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10...

Page 12: ...ating Temperature 6 20 to 100 Baseplate Ambient temperature min 20 20 to 100 100 20 to 90 100 100 83 Storage Temperature 40 to 100 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No d...

Page 13: ...en collector output Environment Operating Temperature 6 20 to 85 Baseplate Ambient temperature MIN 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No d...

Page 14: ...midity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1 h each Shock 196 1m s In package Coo...

Page 15: ...ating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1h each Shock 196 1m s In pack...

Page 16: ...gulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100 150 240 280 Voltage Adjustable Range 10 20 20 60 Function Over Current Protection 4 105 140 Over Voltage P...

Page 17: ...wdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1 h each Shock 196 1m s In package Cooling 7 Conduction cooled Isolation Withstand Voltage Input...

Page 18: ...0 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X...

Page 19: ...ting Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1h each Shock 196 1m s In packa...

Page 20: ...50 4 Voltage Setting Accuracy 1 1 Maximum Line Regulation 2 mV 20 48 60 96 112 Maximum Load Regulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100 150 240 280...

Page 21: ...ting Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 5...

Page 22: ...ltage Setting Accuracy 1 1 Maximum Line Regulation 2 mV 20 48 60 96 112 Maximum Load Regulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100 150 240 280 Voltage...

Page 23: ...Environment Operating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At...

Page 24: ...o dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz amplitude sweep for 1min 0 825mm constant maximum 49 0m s X Y Z 1h each Shock 196 1m s In package Cooling 7 Conduction...

Page 25: ...W 60 90 150 151 2 Voltage Setting Accuracy 1 1 Maximum Line Regulation 2 mV 20 48 60 96 112 Maximum Load Regulation 3 mV 40 96 120 192 224 Temperature Coefficient 0 02 Maximum Ripple Noise 9 mVp p 100...

Page 26: ...30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no operating 10 55Hz sweep for 1min Amplitude 0 825mm constant maximum 49 0m s X Y Z 1h each Shock 196 1m s Cooling 7 Conduction coo...

Page 27: ...tput Environment Operating Temperature 6 20 to 85 Baseplate Ambient temperature min 20 Storage Temperature 40 to 85 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibratio...

Page 28: ...ure 6 20 to 100 Baseplate Ambient temperature min 20 20 to 85 100 100 80 Storage Temperature 40 to 100 Operating Humidity RH 30 95 No dewdrop Storage Humidity RH 10 95 No dewdrop Vibration At no opera...

Page 29: ...er chassis mounting FG Screws must not pro trude into power module by more than 12 7mm Back side for heat sink C Input and output terminal 4 2 8 0 6 PH100S Packege Type T62 See note B See note C See n...

Page 30: ...are shown here in accordance with the specifications B M3 tapped holes 4 for customer chassis mounting FG Screws must not protrude into power module by more than 12 7mm Back side for heat sink C Inpu...

Page 31: ...country of manufacture and safety marking UL C UL BSI CE marking are shown here in accordance with the specifications B M3 tapped holes 4 for customer chassis mounting FG C Input and output terminal 6...

Page 32: ...en input interruption is less than 1s for PH50S 75S 100S and 150S series In case of input interruption please use F type PHs Sequence Time Chart PH50S 75S 100S 150S 300S 600S OVP Trip INPUT ON INPUT O...

Page 33: ...ence Time Chart PH75F 100F 150F 300F Input Voltage Output Voltage L L L IOG H H H L H L H 1 ON OFF Control 1 Level 4 H 35 V or Open 0 L 0 8 V or Short 2 7 10 VDC 2 AUX OCP Set Point INPUT ON REMOTE OF...

Page 34: ...en the unit is operating keep your hands and face away from the unit You may get injured by an accident Caution Confirm that connections to input output terminals and signal terminals are correct as i...

Page 35: ...ow ESR type Nippon Chemi con capacitors or equivalent are recommended For 24V input use LXY Series For 48V input use LXV Series For 110V and 280V input use KMG Series L1 To reduce ripple current at C1...

Page 36: ...g the external trimmer variable resis tor However note that OVP Over Voltage Protection will be activated when the output voltage is raised over specifi cation range Furthermore when the output voltag...

Page 37: ...ted within 60 20 2V 3V 20 of nominal voltage range However note that OVP will be activated when output voltage is raised over specification range Furthermore when the output voltage is adjusted to hig...

Page 38: ...TRM VR Load R1 Figure2 7 Connection Example of External Resistor In the same way remote sensing wires can be connected to load terminal input Changing Output Voltage by Applying External Reference Vol...

Page 39: ...C Input 25VDC 10VDC 280VDC Input 90VDC 25VDC Table7 1 Input Voltage to Release OVP 8 THERMAL PROTECTION Thermal protection is provided This function activates for abnormal ambient temperature rise and...

Page 40: ...each module should not exceed specifications By setting accuracy of output voltage of each power mod ule in parallel operation within 1 the maximum load current can be used up to 95 of nominal output...

Page 41: ...seplate temperature below 85 at actual operating conditions operation is possible For details of thermal design refer to Application Note Thermal Design OPERATING HUMIDITY Note that dew condensations...

Page 42: ...ut and baseplate at 500VDC Figure22 1 Insulation Test VIBRATION Refer to Application Note Installation Power Module Vibration specification value is the value when Power Module alone is mounted on Pri...

Page 43: ...h a common mode choke coil at input of each power module Accuracy of output voltage adjustment shall be within 1 The maximum load current shall be less than 95 of nomi nal output current Ground of PC...

Page 44: ...s damaged or failed 1 No Output Is the rated input voltage supplied Are the ON OFF control terminal remote sensing terminal and output volatage trimming terminal con nected correctly For adjusted outp...

Page 45: ...nsidered as an energy hazard 240VA power and 2V voltage and must not be accessible to a user End equipment manufacturers must provide protection against inadvertent contact with the output terminal on...

Page 46: ...o en sure the safety operation and to acquire safety standard approvals attach an external fuse The external fuse must be fast blow type and be attached to each module indi vidually Furthermore attach...

Page 47: ...o Vo 3 3V 5V 12V 15V 24V 28V 48V 300S 600S 6 3V 6 3V 4700 F 10000 F 10V 10V 3900 F 4700 F 25V 25V 1000 F 2200 F 25V 25V 1000 F 2200 F 35V 35V 560 F 1000 F 50V 50V 470 F 820 F 50V 50V 1 470 F 2 1 680 F...

Page 48: ...V 48V Output 12V 15V 24V 48V Output 12V 15V 24V 48V Output 3 3V 5V 48V Output 3 3V 5V 48V Output 12V 15V 24V 48V Output 12V 15V 24V 48V Output 36 Figure2 1 Limit of Input Voltage Connection method of...

Page 49: ...than 100ms To check OVP function apply an external voltage that is limited to upper limit of maximum OVP range Refer to specification for OVP range Avoid to apply over voltage not to damage the unit I...

Page 50: ...void such a damage ensure all the terminals are con nected before input is applied CS Signal CS Negative voltage based on Vo is generated for CS termi nal Using this signal it is possible to operate i...

Page 51: ...y condi tions it makes each terminal oxidize Hence the quality of the soldering would be worse Cooling Method Various cooling method can be used since the operating temperature is specified by basepla...

Page 52: ...onfirm its performance For details please refer Power Module Appli cation Note Please refer to Power Module Application Note for thermal design and mounting direction Confirm the following items befor...

Page 53: ...e load currents 2 PRECUATIONS There are several basic cautions and warnings in parallel operation of PH300S 600S series Externally attach a control circuit of parallel operation in each power module A...

Page 54: ...sistance rate of copper and approximately 4000 ppm For CS terminal voltage is a small voltage in negative polarity Op Amp A1 1 2 is amplifier inverting shown as Figure3 2 For all of PH modules to be i...

Page 55: ...refer to values expressed in Fig ure3 2 and values for each component shown in Table3 2 The tolerance shall be less than 5 Values for each Component Values of Capacitor C1 Resistor R1 R4 R18 R20 R23...

Page 56: ...output voltage Control Circuit of Parallel Operation Control Circuit of Parallel Operation Load Figure5 2 Parallel Operation at programmed ouput voltage c Parallel Operation with adjustable output vo...

Page 57: ...ange Control Circuit of Parallel Operation Control Circuit of Parallel Operation Load Figure6 2 N 1 Redundant Operation at programmed output voltage fixed c N 1 Redundant Operation with adjustable out...

Page 58: ...B 356...

Reviews: