PH
B-302
・All specifications are subject to change without notice.
PH300F24
PH
100F24
ITEMS/UNITS
MODEL PH100F24-2 PH100F24-3 PH100F24-5 PH100F24-12 PH100F24-15 PH100F24-24 PH100F24-28
Input
Voltage Range
V
DC18 - 36
Efficiency (typ)
(*1)
%
66
70
80
81
82
83
Current (typ)
(*1) A
2.53
3.57
5.21
5.19
5.11
5.06
Output
Nominal Voltage
VDC
2
3
5
12
15
24
28
Maximum Current
A
20
8.4
6.7
4.2
3.6
Maximum Power
W
40
60
100
100.8
100.5
100.8
Voltage Setting Accuracy (*1)
%
±
1%
Maximum Line Regulation (*2) mV
20
48
60
96
112
Maximum Load Regulation (*3) mV
40
96
120
192
224
Temperature Coefficient
0.02% /
℃
Maximum Ripple & Noise (*9) mVp-p
100
150
240
280
Voltage Adjustable Range (*10)
±
20%
+20%, -60%
Function
Over Current Protection (*4)
105% - 140%
Over Voltage Protection (*5)
165% - 240%
125% - 145%
Remote Sensing
(*8)
Possible
Remote ON/OFF Control (*8)
Possible (SHORT: ON OPEN: OFF)
Parallel Operation
(*8)
Possible
Series Operation
(*8)
Possible
I.O.G. Signal
(*8)
Possible (Open collector output)
Environment
Operating Temperature (*6)
℃
- 20 to + 85 (Baseplate) ambient temperature MIN = - 20
Storage Temperature
℃
- 40 to + 85
Operating Humidity
%
RH
30 - 95 (No dewdrop)
Storage Humidity
%
RH
10 - 95 (No dewdrop)
Vibration
At no operating, 10-55Hz (sweep for 1min)
Amplitude 0.825mm constant (maximum 49.0m/s²) X, Y, Z 1h each
Shock
196.1m/s² (In package)
Cooling
(*7)
Conduction cooled
Isolation
Withstand Voltage
Input-Baseplate : 2kVAC, Input-Output : 2kVAC (20mA) for 1min
Output-Baseplate : 500VDC (100mA) for 1min
Isolation Resistance
More than 100Mohm at 25
℃
and 70%RH Output-Baseplate...500VDC
Standards Safety Standards
Approved by UL60950-1, CSA C22.2 No.60950-1, EN60950-1
Mechanical
Weight (typ)
g
180
Size (W x H x D)
mm
83 x 12.7 x 86 (Refer to outline drawing)
PH100F24 Specifications
(*1) At 24VDC and maximum output current.
(*2) 18 - 36VDC, constant load.
(*3) No load - full load, constant input voltage.
(*4) Constant current limiting with automatic recovery.
(*5) Inverter shutdown method, manual reset.
(*6) Ratings - Refer to derating curve below.
- Load(%) is percent of maximum output current.
(*7) Heatsink has to be chosen according to instruction manual.
(*8) Refer to instruction manual.
(*9) External components are needed for operation.
(Refer to basical connection and instruction manual.)
(*10) At 24VDC input.(Refer to instruction manual.)
0
20
40
60
80
100
−20
0
20
40
60
80
85
100
型名 PH100F24
Baseplate Temperature(℃)
Load
(%)
Derating Curve