Kinergier pro bi-directional inverter User Manual
TBB Power Co., Ltd
40
General data
Transfer time
<2ms(<15ms when WeakGrid Mode)
Remote on-off
Yes
Programmable relay
2x
Protection
a) output short circuit
b) overload
c) battery voltage too high
d) battery voltage too low
e) temperature too high
f) input voltage out of range
g) input voltage ripple too high
CAN Bus communication port
For parallel and three phase operation,
remote monitoring and system integration
General purpose com. Port
RS485,Bluetooth,GPRS,WLAN
Operating temperature range
-20 to +60
˚
C
Storage temperature range
-40 to +70
˚
C
Relative humidity in operation
95% without condensation
Mechanical Data
Dimension
530mm
*285mm
*185mm
530mm
*285mm
*185mm
530mm
*285mm
*185mm
Net Weight
40KG
Cooling
Forced fan
Protection index
IP20