Kinergier pro bi-directional inverter User Manual
TBB Power Co., Ltd
20
5.4.3
5.4.3
Connect
Connect
in
in
put
put
dry
dry
contact
contact
The input dry contact is connected by default with a short-circuit terminal for EPO control.
After the terminal is removed, the inverter stops working. If there is no special case, do not
remove the terminal.
5.4.4
5.4.4
Connecting
Connecting
parallel
parallel
synchronous
synchronous
communication
communication
cable
cable
In single mode, please keep the resistance matching crystal that is inserted to the "ComSyncIn"
interface.
In the parallel mode, please keep the resistance matching crystal that is inserted to the
"ComSyncIn" interface of the first unit and "ComSyncOut" interface of the last unit, and
remove the resistor matching crystal of other units, connect the adjacent units by a standard
8P8C network cable, the "ComSyncOut" interface of the previous units is connected to the
"ComSyncIn" interface of the next machine.