Kinergier pro bi-directional inverter User Manual
TBB Power Co., Ltd
4
2.3.4
2.3.4
Transfer
Transfer
In case of voltage/frequency/waveform of AC input match the minimum quality, the voltage
will be switched directly to AC output. Kinergier pro bi-directional inverter will switch off,
battery charger switching on and load being powered by AC input. You will have at the output
the same voltage as AC input.
In case of AC input failure or exceeding the maximum AC input current set by the user,
Kinergier pro bi-directional inverter will initiate a quick switching to inverter, of which will
guarantee an undisturbed power for majority of the appliance. Upon AC input resume or
match the quality, it will switch back again. With this mode, Kinergier pro bi-directional
inverter could be used as an UPS.
2.3.5
2.3.5
Battery
Battery
t
t
ype
ype
s
s
ettings
ettings
The AGM, GEL/OPzV battery types can be selected through the LCD, and the charging
voltages of different battery types are different. The battery type is set to GEL by default.
Specific electrical parameters can also be adjusted through the LCD.
2.3.6
2.3.6
Battery
Battery
l
l
ow
ow
v
v
oltage
oltage
s
s
hutdown
hutdown
t
t
hreshold
hreshold
set
set
Depending on the battery type and application, the user can set different battery low-voltage
shutdown points (LVD) through the LCD.
2.3.7
2.3.7
Weak
Weak
grid
grid
mode
mode
In the application environment where the AC input voltage is severely low, it may be in an
inverter state for a long time and battery can't be charged. Resulting in a serious undercharge
of the battery and failure to supply power to the device. The user can set the weak grid mode
and voltage range through the LCD, and it can continue to supply power to the load from the
AC input when the grid voltage is low while charging the battery.
2.3.8
2.3.8
Generator
Generator
mode
mode
If the low power AC generator, the output voltage of the generator is unstable or the waveform
is severely distorted. It will always work in inverter mode, user can set the generator mode
through the LCD screen, Reduce the requirements of AC input power quality (such as voltage,
frequency and waveform), it will continue to work in AC mode.
2.3.9
2.3.9
Power
Power
search
search
mode
mode
In the case where the inverter is allowed to work intermittently, the threshold of the power
search mode can be set through the LCD. In the power search mode, the no-load power
consumption will be reduced by about 70%. The threshold of the power search mode can be
adjusted from 0.25% to 1% of rated power.