Kinergier pro bi-directional inverter User Manual

TBB Power Co., Ltd

30

>Para_Battery

U_Float_CHG

11.5V ~ U_AVE_CHG

14.5V max

Floating

voltage

of

single battery (battery
size is 12V/section)
Note:

This

value

is

affected when changing
the battery type and can
be

reconfigured

as

needed.

U_DisCHG_End

9V ~ (BAT_LV_Protect - 0.3)

11V max

Secondary undervoltage
protection for single-cell
battery (battery size is
12V/section)

BAT_LV_Protect

(U_DisC 0.3) ~
(min(LV_PRO_Recover,
BAT_LV_Warn) - 0.3)
(Range:9.5~12V)

Undervoltage protection
for

single

battery

(battery

size

is

12V/section)

BAT_LV_Warn

(BAT_LV_P 0.3)~13V
(10V min)

Undervoltage

warning

for

single

battery

(battery

size

is

12V/section)

BAT_OV_Warn

(BAT_L 0.3)~15V
(12V min)

Overvoltage alarm for
single battery (battery
size is 12V/section)

SYS_CHG_MaxCur

5~100A

System

maximum

charging current
Note:

This

value

is

affected when changing
the battery capacity and
battery type, and the
user can reconfigure it
according

to

the

requirements.

E2F_Delay

1~600min

Minimum Bulk time

Max_ABS0RP_Time

1~240h

Maximum

Absorption

time

Auto_CHG_Cycle

24~2400h

Equalization cycle time

CHG_TEMP-Coef

0~20mv/

/cell

Charging

temperature

compensation
coefficient

CHG_TEMP_OMPE_EN

1-on; 0-off

enable

the

charging

temperature
compensation

LV_PR0_Recover

(BAT_LV_P 0.3) ~
14.5V

Undervoltage protection
recovery value

Summary of Contents for Kinergier Pro CK 4.0S

Page 1: ...Kinergier pro bi directional inverter User Manual TBB Power Co Ltd Kinergier Pro series Bi directional inverter Version V1 0 Date Mar 2019...

Page 2: ...Kinergier pro bi directional inverter User Manual TBB Power Co Ltd...

Page 3: ...ional inverter User Manual TBB Power Co Ltd WARNING FIRE HAZARD SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON COMBUS TIBLE SURFACE ONLY CAUTION THE DC AND AC BREAKER MUST HAVE BEEN TURNED OFF BEFORE...

Page 4: ...is manual were suitable for Kinergier pro bi directional inverter This chapter contains important safety and operation instructions Read and keep this User Guide well for later reference The Kinergier...

Page 5: ...2 3 8 Generator mode 4 2 3 9 Power search mode 4 2 3 10 Protect function 5 2 3 11 Dry contact 6 2 3 12 RS485 6 2 3 13 CAN 6 2 3 14 Parallel function 6 2 3 15 Power assist function 6 2 3 16 Battery pr...

Page 6: ...cable 21 5 4 6 Connect the monitor communication cable 21 5 4 7 Connect input dry contact 21 6 Operation of Kinergier Pro 22 6 1 Button description 22 6 2 Menu introduction 23 6 3 Initial interface 24...

Page 7: ...indoor use DO NOT block off ventilation otherwise the Kinergier pro bi directional inverter would be overheating To avoid fire and electric shock make sure all cables selected with right gauge and be...

Page 8: ...power management functions devices make it convenient to compose different advanced hybrid independent power systems It has the characteristics of small size strong carrying capacity and high intelli...

Page 9: ...3 3 Charger Charger Multi stage charging The multi stage battery charging management function can quickly fill the battery and effectively extend the battery life Automatic charging temperature compe...

Page 10: ...n t threshold hreshold set set Depending on the battery type and application the user can set different battery low voltage shutdown points LVD through the LCD 2 3 7 2 3 7 Weak Weak grid grid mode mod...

Page 11: ...tate after the internal temperature returns to normal it can automatically resume normal operation Short circuit protection The equipment will automatically shut down when the AC output is shorted and...

Page 12: ...phase parallel system which is convenient for flexible expansion of power capacity and construction of a micro grid system to meet different application requirements 2 3 15 2 3 15 Power Power assist a...

Page 13: ...itical loads AC OUT2 defaults to secondary loads when grid or generators are normal and when grid or generators are abnormal the AC OUT2 disconnect its load User can also set the AC OUT2 on off logic...

Page 14: ...directional inverter User Manual TBB Power Co Ltd 8 3 3 Structure Structure 3 1 3 1 Product Product draw draw 3 1 1 3 1 1 Kinergier Kinergier pro pro bi directional bi directional inverter inverter 1...

Page 15: ...gier pro bi directional inverter User Manual TBB Power Co Ltd 9 3 2 3 2 Product Product size size 3 2 1 3 2 1 Kinergier Kinergier pro pro bi directional bi directional inverter inverter 1 CK 4 0S 6 0S...

Page 16: ...User manual 1 7 8P8C communication cable 2m 1 8 4P4C communication cable 2m 1 The equipment should be transported to the installation site and then the outer packaging should be removed Check the var...

Page 17: ...ents following the Tab in advance Classify Tools and instruments Installing Percussion drill 8mm Diagonal pliers Wire stripper Wire cutters 25mm 35mm Hydraulic pliers 25mm 35mm Cross screwdrivers M4 M...

Page 18: ...ease install the equipment in a location of dry clean cool with good ventilation Operating temperature 20 60 Storage temperature 40 70 Cooling Force fan Relative humidity in operation 95 without conde...

Page 19: ...recommend connecting a DC fuse corresponding to the conductor between battery and Kinergier pro bi directional inverter which will offer protection to the battery cable Please refer to following chart...

Page 20: ...d be installed either vertically on wall or horizontally on floor Take the case of installing on the wall as an example please choose a flat surface to fix the unit securely Step1 Punch the wall accor...

Page 21: ...Kinergier pro bi directional inverter User Manual TBB Power Co Ltd 15 Step 2 Step3 Step 4...

Page 22: ...battery voltage matches the model you are going to install the wrong battery could destroy equipment and is out of warranty Please double confirm the polarity of battery input Reverse polarity couldc...

Page 23: ...screwdriver AC output cable Refer to section 4 2 to select the appropriate wire Pass the AC output cable through the front panel confirm L N and PE and tighten the screws with a screwdriver PE cable R...

Page 24: ...Tem BTS battery temperature sensor B Remote ON OFF Remote ON OFF control C DryInput Input Dry control D ComSyncIn Parallel synchronous communication input CAN E ComSyncOut Parallel synchronous commun...

Page 25: ...battery temperature sensor and attach the sensor to the center of the side of the battery to ensure a firm bond Please notice the cable supplied is around 3000mm Do not pull cable too hard avoid loos...

Page 26: ...rallel parallel synchronous synchronous communication communication cable cable In single mode please keep the resistance matching crystal that is inserted to the ComSyncIn interface In the parallel m...

Page 27: ...6 5 4 6 Connect Connect the the monitor monitor communication communication cable cable Connect the external monitor device to the ComMON interface through the 4P4C communication cable 5 4 7 5 4 7 Co...

Page 28: ...on self test is completed the machine is in the standby state Press the ON OFF button for more than 2s to turn on the inverter Press the switch button for more than 2s to turn off the inverter the who...

Page 29: ...Kinergier pro bi directional inverter User Manual TBB Power Co Ltd 23 6 2 6 2 Menu Menu introduction introduction...

Page 30: ...LCD will establish contact with the Inverter If there is a communication failure the communication fault will be displayed 6 4 6 4 Real time Real time information information interface interface The L...

Page 31: ...level menu Press the button on the first level menu to enter the corresponding 2nd level menu Some 2nd level menus can enter the 3rd level menu Press the to return the upper level menu Running Info En...

Page 32: ...pages The first line is the corresponding code for the fault or warning flag The second line is specific information Displayed when there is no fault History Records Enter to see history record inform...

Page 33: ...6 6 6 6 Parameter Parameter setting setting interface interface 6 6 1 6 6 1 Operating Operating i instructions nstructions Note Some parameter settings are only allowed to be set when the Equipment is...

Page 34: ...he unit s phase Parallel_Address 1 8 Set the unit s parallel address Common_BAT_SYS 1 Common battery pack system 0 Distributed Battery Pack System Set the system s battery pack mode Para_Mode Display...

Page 35: ...uzzer silent mode is enable 1 Buzzer silent mode is disable Whether the inverter s buzzer sounds when the MPPT alarms Para_lnverter Display Setting range Description INV_Output_Volt 200 240V Inverter...

Page 36: ...V_Warn BAT_LV_Protect 0 3 13V 10V min Undervoltage warning for single battery battery size is 12V section BAT_OV_Warn BAT_LV_Warn 0 3 15V 12V min Overvoltage alarm for single battery battery size is 1...

Page 37: ...apt 0 Normal Grid 1 Weak Grid AC in harmonic adaptation mode Note When the AC in input harmonic is too large and the inverter cannot track its phase select 1 to give the inverter a greater chance to t...

Page 38: ...ssword Setup Wizard See 6 8 Reset Parameter Display Description Reset User_Para Restore the user s default parameters Clear EnergyLog Display Description Clear Ener gyLog Clear the electricity statist...

Page 39: ...Kinergier pro bi directional inverter User Manual TBB Power Co Ltd 33 6 7 6 7 User User config config 6 7 1 6 7 1 Solar Solar Config Config...

Page 40: ...lly open state to the normally closed state when machine overload alarm or failure 1 Gen Driver Generator start and stop control reserved 2 Other Logic Reserved 6 7 4 6 7 4 ACout2 ACout2 Control Contr...

Page 41: ...le Page_Turn_Auto Automatically page turning time of the real time information display interface 3 30s Page_Turn_Pause Dwell time of the real time information display interface 3 180s Menu_Exit_Auto I...

Page 42: ...wer supply is abnormal 5 T_HS_OT Heat sink s temperature is too high 6 T_TX_OT Transformer s temperature is too high 7 Sam_HD_Fault Sampling is abnormal 8 EEPROM_Fail EEPROM is abnormal 9 Output_SC Ou...

Page 43: ..._Fault Fan is abnormal 9 Par_Connect Parallel running is abnormal 10 CommParCan_Err CAN communication error is abnormal 11 Par_ID_Conflict Parallel address conflict 12 ParaSet_Conflict Parameter do no...

Page 44: ...s Turned off from standby Inverter off The Inverter is off Inverter on The Inverter is on Inverter charge The Inverter is in charging mode Inverter GCI The Inverter is in GCI mode Inverter bypass The...

Page 45: ...dc Output Output voltage 220 240 VAC 2 Frequency 45 60 Hz 0 05 Harmonic distortion THDV 2 THDI 5 Cont output power at 25 C 3000W 4500W 6000W Power factor 1 0 Peak power 30min 4000W 6000W 8000W Peak po...

Page 46: ...f input voltage out of range g input voltage ripple too high CAN Bus communication port For parallel and three phase operation remote monitoring and system integration General purpose com Port RS485 B...

Page 47: ...Kinergier pro bi directional inverter User Manual TBB Power Co Ltd 41...

Page 48: ...Kinergier pro bi directional inverter User Manual TBB Power Co Ltd 42 TBB Power Co Ltd Web www tbbpower com Tel 86 592 5212299 Fax 86 592 5796070 Email service tbbpower com...

Reviews: