Kinergier pro bi-directional inverter User Manual
TBB Power Co., Ltd
30
>Para_Battery
U_Float_CHG
11.5V ~ U_AVE_CHG
(
14.5V max
)
Floating
voltage
of
single battery (battery
size is 12V/section)
Note:
This
value
is
affected when changing
the battery type and can
be
reconfigured
as
needed.
U_DisCHG_End
9V ~ (BAT_LV_Protect - 0.3)
(
11V max
)
Secondary undervoltage
protection for single-cell
battery (battery size is
12V/section)
BAT_LV_Protect
(U_DisC 0.3) ~
(min(LV_PRO_Recover,
BAT_LV_Warn) - 0.3)
(Range:9.5~12V)
Undervoltage protection
for
single
battery
(battery
size
is
12V/section)
BAT_LV_Warn
(BAT_LV_P 0.3)~13V
(10V min)
Undervoltage
warning
for
single
battery
(battery
size
is
12V/section)
BAT_OV_Warn
(BAT_L 0.3)~15V
(12V min)
Overvoltage alarm for
single battery (battery
size is 12V/section)
SYS_CHG_MaxCur
5~100A
System
maximum
charging current
Note:
This
value
is
affected when changing
the battery capacity and
battery type, and the
user can reconfigure it
according
to
the
requirements.
E2F_Delay
1~600min
Minimum Bulk time
Max_ABS0RP_Time
1~240h
Maximum
Absorption
time
Auto_CHG_Cycle
24~2400h
Equalization cycle time
CHG_TEMP-Coef
0~20mv/
℃
/cell
Charging
temperature
compensation
coefficient
CHG_TEMP_OMPE_EN
1-on; 0-off
enable
the
charging
temperature
compensation
LV_PR0_Recover
(BAT_LV_P 0.3) ~
14.5V
Undervoltage protection
recovery value