Kinergier pro bi-directional inverter User Manual
TBB Power Co., Ltd
31
>Para_Acln
Display
Setting range
Description
E_ACin_Priority
0-DC First
1-AC First
2-User Config
Read only
Change according to the
configuration of ACin
Config in user config
AC_U_Max
220~260V
Maximum AC in input
voltage
AC_U_Min
165~220V
Minimum AC in input
voltage
AC_F_Max
Rate_A (0 ~ 5)Hz
Maximum AC in input
frequency
AC_F_Min
Rate_AC_Freq - (0 ~ 5)Hz
Minimum AC in input
frequency
Harmomic_Adapt
0- Normal Grid
1- Weak Grid
AC
in
harmonic
adaptation mode.
Note: When the AC in
input harmonic is too
large and the inverter
cannot track its phase,
select 1 to give the
inverter a greater chance
to track the phase of the
AC in.
PowerAssist_Cur
3~50A
The maximum current
allowed for AC in input,
that is, when the input
current of ACin reaches
this set value, the excess
energy required by the
load will be taken from
the battery.
Feedback_EN
0- Forbid
1- Allow
Whether
to
allow
energy to be fed back to
ACin (read only)
Feedback_MaxCur
0~50A
Maximum
current
allowed to feed back to
grid
AC-Connect Delay
20~300s
Delay time into the grid
after AC in is detected to
be normal