>ACout2 Logic
Logic Mode
0- Default
Logic Mode
2- Time Ctrl
>Logic Mode
ACout2 ON Timer
<Back>
>Timer1 EN Set
Timer1 On/Off
Timer1 En Set
0-Disable
Startup Time
00:00
Shutdown Time
23:59
Timer2 EN Set
>Timer2 On/Off
.....
Logic Mode
1- Ubat Ctrl
Logic Mode
>ACout2 ON/OFF
<Back>
ACout2 OFF Ubat
11.5V
ACout2 ON Ubat
13.5V
ACout2 OFF Delay
30s
ACout2 ON Delay
180s
Logic Mode
3- PV_INV Ctrl
Logic Mode
1- SOC Ctrl
Logic Mode
>ACout2 ON/OFF
<Back>
ACout2 OFF SOC
30%
ACout2 ON SOC
50%
ACout2 OFF Delay
30s
ACout2 ON Delay
180s
This mode is not applicable to TBB
SUPER-L lithium battery.
This mode is applicable to TBB
SUPER-L lithium battery.
ACout2 OFF SOC
:
Turn off the
SOC threshold of the ACout2.
ACout2 ON SOC
:
Turn on The
SOC threshold of the ACout2.
ACout2 OFF Ubat
:
Turn off the
voltage threshold of the ACout2.
ACout2 ON Ubat
:
Turn on the
voltage threshold of the ACout2.
5.6.5 Screen Set
Backlight _KeepOn
Enable the backlight fixed lighting function
0-Disable
1-Enable
Default:
0-Disable
Page_Interval
To set automatic page turning time to display the real-time information,
3~30s.
Default:
5s
5.6.6 Date & Time
Set the current Date & Time.
5.6.7 Trigger Command
Fault Unlock
Unlock the fault, and the inverter can be restarted.
Fan Dedusting
Clear cnergy calculation data.
BAT Dischg Test
Parameter Sync
In a parallel or three phase system, the slave inverter can use the
function to synchronize its parameters with that of the master inverter.