Kinergier Pro User Manual
22
Solar System
sub-menu offers the approach to compose DC Couple or AC Coupled PV Systems
using Kinergier Pro.
When you are composing the DC Coupled PV System, all the parameters you configure with
Kinergier Pro will be updated automatically with Solar Mate MPPT.
For parallel system, only the Master unit need to be configured.
Solar System:
Solar System
Item
Setting range
Description
Solar_System
0-N/A
1-DC Couple
2-AC Couple
3-DC+AC Couple
Select Solar system you are
intending to compose.
DC Coupled PV System: using
Solar mate series MPPT
Charger.
AC Coupled PV System: using
IG series PV Inverter
Default:
0-N/A
MPPT_CHG_Num
1~6
Number of Solar Mate MPPT
connected.(Only applicable for
DC Coupled PV System)
Default:
1
PV_Inverter_Num
1~2
Number of IG PV inverter
connected. (Only applicable for
AC Coupled PV System)
Default:
1
FREQ_Drop
Set--->
Drop_Start_FREQ
50.1~51.0Hz
(@50Hz)
60.1~61.0Hz
(@60Hz)
Drop Start Freq
:
When the frequency reaches
this set value, the PV inverter
starts to derate.
Default
: 50.85Hz
FREQ_Drop
Set--->
Drop_Stop_ FREQ
51.1~53.5Hz
(@50Hz)
61.1~63.5Hz
(@60Hz)
Drop Stop Freq:
When the frequency reaches
this set value, the PV inverter
derates to the minimum power.
Default
: 53.05Hz
FREQ_Drop
Set--->
Disconnect_ FREQ
51.5~54.5Hz
(@50Hz)
61.5~64.5Hz
(@60Hz)
Disconnect Freq:
When the frequency reaches
this set value, the PV inverter
has no output.
Default
: 54.15Hz
BGK System
sub-menu offers the approach to compose the BGK parameter.
If you choose the relevant BGK you installed, Kinergier Pro will trigger on the function of BGK.
For battery bank composed by 2V cells, you need BGK Master and BGK-02.