![TBB power Kinergier Pro Series Manual Download Page 33](http://html2.mh-extra.com/html/tbb-power/kinergier-pro-series/kinergier-pro-series_manual_4375271033.webp)
Kinergier Pro User Manual
28
EQ Ctrl_Set (This function is only applicable for the flooded battery and traction battery.)
EQ Ctrl_Set
Item
Setting range
Description
EQ_Command
0-OFF
1-ON
EQ charging Switch
When choosing 1, you can turn on the
EQ charging and it will auomaticlaly quit
after performing the EQ charging.
it can be manually shut down at any time
after choosing 0.
Default
: 0-OFF
EQ_Voltage
15.5~16.3V
User can change the EQ voltage for
flooded and traction battery.
Default
: 15.5V(Flooded)
16.2V(Traction)
EQ_Sustain_Time
30~90min
User can change the EQ timer for
flooded and traction battery.
Default
: 30min
5.5.2.4 Para_Inverter
Para_Inverter:
You can configure the output of the inverter through this menu.
Para_Inverter
Item
Setting range
Description
INV_Output_VOLT
200~240V
Inverter output voltage RMS.
Default
: 230V
INV_Output_FREQ
50/60Hz
Rated AC frequency.
Default
: 50Hz
5.5.2.5 Para_ACin:
This menu is for setting the AC input parameters of the inverter.
Para_ACin
Item
Setting range
Description
ACin_Source_SEL
0-Grid
1-Generator
Select the ACin Source.
When “1-Generator” is selected, the
parameter “Common N” is Enabled and
“GND connect “is Disabled.
Default
: 0-Grid
ACin_U_Max
240~265V
@230Vac Model
120~140V
@120Vac Model
Maximum AC in input voltage
Default
:
265V@230Vac Model
140V@120Vac Model
ACin_U_Min
145~200V
@230Vac
Minimum AC in input voltage
Default
:
Summary of Contents for Kinergier Pro Series
Page 1: ......