- 41 -
Operation 7
Press the
arrow
key and select the
Set ?
.
Display (line 2):
Set ?
Operation 8
Press the
ENTER
key and define the command.
Display (line 2):
Disable?
Operation 9
Press the
ENTER
key and define the command.
Display (line 2):
Complete
5.1.2.3 RtyCnt value in the CLNROL-function
You can choose the RtyCnt value in the CLNROL-function. RtyCnt means the number of the
picking or putting error restoration in the transporter operation.
When the number of the picking or putting error restoration exceed
s
the set RtyCnt value, the
Alarm LED is blinking and "
REQ CLNROL
" message is displayed on the LCD.
5.1.2.4 Changing the RtyCnt value
Default RtyCnt value : 15
The procedure described below is the operation in case of changing the RtyCnt from default
value (=15) to 25.
Operation Example
Operation 1
Switch ON the power and wait for the completion of power-on test.
Display:
READY
and
DRV empty
are alternately displayed.
Operation 2
Press the
ENTER
key.
Display:
STATUS
Operation 3
Press the
arrow
key and select the
MAINTENANC
command
Display
:
MAINTENANC
Operation 4
Press the
ENTER
key and define the command.
Display (line 1):
PASSWORD
Display (line 2):
0000000000