Crimp Connectors
Caution
Always use crimp connectors for the CPM1A’s power lines and I/O lines or else
use a single-wire line (instead of a stranded wire). Do not connect bare stranded
wires directly to terminals. Bare stranded wires connected directly to the termi-
nal can cause a fire.
Use M3 terminal screws and tighten the screws securely (0.5 N
S
m).
6.2 mm max.
6.2 mm max.
Fork terminal
Ring terminal
1-4-5 Output Wiring
Relay Output Wiring
Wire the outputs to the CPM1A’s CPU Unit and Expansion I/O Module as shown
in the following diagrams. Use crimp connectors or single-wire lines (not
stranded wire) to connect to the PLC. The power supply output terminals can be
used with AC-type CPU Units.
·
Always use single wire or attach crimp connectors if a stranded wire is used.
·
Don’t exceed the output capacity or the maximum common current. Refer to
NO TAG I/O Specifications
for details.
Item
Specification
Output capacity
2 A (250 VAC or 24 VDC)
Max. common capacity
2 A/output
Max. unit capacity
CPM1A-20CAR-A: 16 A
CPM1A-32CAR-A: 20 A
Output Configurations
CPM1A-20CAR-A
Outputs may be wired individually or on a common as shown.
CPM1A-32CAR-A
Outputs may be wired individually or on a common as shown.
Commons
Commons
Common
Wiring and Connections
Section 3-4
Summary of Contents for CPM1A-20CAR-A
Page 3: ...ii...
Page 5: ...iv...
Page 9: ...iv...
Page 29: ...14 System Configuration Section 1 2...
Page 43: ...29 Unit Components Section 2 2...
Page 65: ...51 Wiring and Connections Section 3 4...
Page 123: ...Appendix B Dimensions 2 CPM1 CIF01 90 81 21 30 205 50 56 CPM1 CIF11 90 81 21 30 205 50 61...
Page 124: ...Appendix B Dimensions 3 Dimensions with Peripheral Devices Attached Approx 90 Approx 125...
Page 125: ...Appendix B Dimensions 4...