92
5 -3 S elf -diagnosis Functions
The CPM1A is equipped with a variety of self-diagnosis functions to help identify
and correct errors that might occur and reduce down time.
PLC errors are divided into 2 categories based on the severity of the errors. Fatal
errors are more serious errors which stop CPM1A operation. Non-fatal errors
are less serious and don’t stop CPM1A operation.
5 -3 -1 Non -fatal Errors
PLC operation and program execution will continue after one or more of these
errors have occurred. Although PLC operation will continue, the cause of the er-
ror should be corrected and the error cleared as soon as possible.
When one of these errors occurs, the POWER and RUN indicators will remain lit
and the ERR/ALM indicator will flash.
Message
FAL No.
Meaning and appropriate response
SYS FAIL FAL**
(** is 01 to 99 or 9B.)
01 to 99 An FAL(06) instruction has been executed in the program. Check the FAL number to
determine conditions that would cause execution, correct the cause, and clear the
error.
9B
An error has been detected in the PC Setup. Check flags AR 1300 to AR 1302, and
correct as directed.
AR 1300 ON: An incorrect setting was detected in the PC Setup (DM 6600 to
DM 6614) when power was turned on. Correct the settings in PROGRAM Mode and
turn on the power again.
AR 1301 ON: An incorrect setting was detected in the PC Setup (DM 6615 to
DM 6644) when switching to RUN Mode. Correct the settings in PROGRAM Mode
and switch to RUN Mode again.
AR 1302 ON: An incorrect setting was detected in the PC Setup (DM 6645 to
DM 6655) during operation. Correct the settings and clear the error.
SCAN TIME OVER
F8
Watchdog timer has exceeded 100 ms. (SR 25309 will be ON.)
This indicates that the program cycle time is longer than recommended. Reduce cycle
time if possible. (The CPM1A can be set so that this error won’t be detected.)
Communication
Errors (no message)
None
If an error occurs in communications through the peripheral port, the COMM indicator
will be off. Check the connecting cables and restart. Check the error flags in AR 0812
ON.
5 -3 -2 Fatal Errors
PLC operation and program execution will stop and all outputs from the PLC will
be turned OFF when any of these errors have occurred. CPM1A operation can’t
be restarted until the PLC is turned off and then on again or a Peripheral Device
is used to switch the PLC to PROGRAM mode and clear the fatal error.
All CPU Unit indicators will be OFF for the power interruption error. For all other
fatal operating errors, the POWER and ERR/ALM indicators will be lit. The RUN
indicator will be OFF.
Self-diagnosis Functions
Section 5 -3
Summary of Contents for CPM1A-20CAR-A
Page 3: ...ii...
Page 5: ...iv...
Page 9: ...iv...
Page 29: ...14 System Configuration Section 1 2...
Page 43: ...29 Unit Components Section 2 2...
Page 65: ...51 Wiring and Connections Section 3 4...
Page 123: ...Appendix B Dimensions 2 CPM1 CIF01 90 81 21 30 205 50 56 CPM1 CIF11 90 81 21 30 205 50 61...
Page 124: ...Appendix B Dimensions 3 Dimensions with Peripheral Devices Attached Approx 90 Approx 125...
Page 125: ...Appendix B Dimensions 4...