![Sysmac CPM1A-20CAR-A Operation Manual Download Page 62](http://html1.mh-extra.com/html/sysmac/cpm1a-20car-a/cpm1a-20car-a_operation-manual_1421659062.webp)
48
The following diagram shows the wiring in the RS-422 cables used to connect
CPM1A PLCs to a 3G2A9-AL004-E Link Adapter. In both the Link Adapter/
RS-422 Adapter connections and the RS-422 Adapter/RS-422 Adapter connec-
tions, connect the SG, RDA, RDB, SDA, and SDB terminals to the same termi-
nals in the other Adapter.
25-pin D-sub Connector
Use a straight RS-232C
cable to connect to the
host computer’s
RS-232C port.
9-pin D-sub Connector
Signal
Pin no.
1
2
3
4
5
6
7
8
9
RDB
--
SG
--
SDB
RDA
FG
--
SDA
3G2A9-AL004-E Link Adapter
RS-422 Adapter
SG
RDA
RDB
SDA
SDB
CPM1A CPU Unit
Note
1. The maximum length of the RS-422 cable should be 500 m.
2. Set the termination resistance switch to “ON” (upper side) for Adapters on
both ends of the Host Link system.
Always use crimp connectors when wiring the RS-422 Adapters. Use M3 termi-
nal screws and tighten the screws securely to the torque of 0.5 N
S
m.
6.2 mm max.
Fork terminal
6.2 mm max.
Ring terminal
Wiring and Connections
Section 3-4
Summary of Contents for CPM1A-20CAR-A
Page 3: ...ii...
Page 5: ...iv...
Page 9: ...iv...
Page 29: ...14 System Configuration Section 1 2...
Page 43: ...29 Unit Components Section 2 2...
Page 65: ...51 Wiring and Connections Section 3 4...
Page 123: ...Appendix B Dimensions 2 CPM1 CIF01 90 81 21 30 205 50 56 CPM1 CIF11 90 81 21 30 205 50 61...
Page 124: ...Appendix B Dimensions 3 Dimensions with Peripheral Devices Attached Approx 90 Approx 125...
Page 125: ...Appendix B Dimensions 4...