伺服產品
/Servo Products
–
Hardware Manual of 30kW Servo Drive II (SPD-32B1-300)
Wiring and Signal
(
30kW SPD
)
–
60
•
•
•
Incorrect Motor Rated Current
Setting
Check the rated current value
Check the input parameters. Re-tune
if modifications are required.
Insufficient of Acc/Dec Time
Check the Acc/Dec parameters
Increase the Acc/Dec Time
Excessive Load
Check if the load rate continues
to exceed 100%
Replace the motor with one of greater
power
Users can observe the temperatures measured by KTY84 through status monitoring variables.
These variables correspond to the measured temperatures as follows:
Parameter
Parameter Descriptions
Pn-D60
Measured Temperature via KTY84 with Syntec Drive
Pn-D61
Measured Temperature via Feedback Syntec Encoder Internal KTY84
Pn-D62
Measured Temperature via Feedback Syntec Encoder External(1) KTY84
Pn-D63
Measured Temperature via Feedback Syntec Encoder External(2) KTY84
Pn-D64
Measured Temperature via Feedback Syntec Encoder External(3) KTY84
Pn-D65
Measured Temperature via 2nd Feedback Syntec Encoder Internal KTY84
Pn-D66
Measured Temperature via 2nd Feedback Syntec Encoder External(1)
KTY84
12.11 Other Wiring Diagrams (30kW SPD)
12.11.1
Syntec Encoder External Analogy Temperature Wiring Diagram
Distinguishing among the PTC130 temperature sensor, the n
ormally closed (NC) contact
, and the KTY84
temperature sensor:
On the label of PTC130 temperature sensor signal line, "PTC130" is labelled right underneath "Thermal
Protection."
On the label of normally closed
(NC) contact
temperature sensor signal line, "(NC)" is labelled right
underneath "Thermal Protection," as in Figure 1.
On the label of KTY84 temperature sensor signal line, "KTY84" is labelled right underneath "Thermal
Protection," as in Figure 2. In addition, the KTY84 motor has a "KTY84" label attached to the motor casing, as
in Figure 3.