Hardware Manual of 30kW Servo Drive II (SPD-32B1-300)
Wiring and Signal
(
30kW SPD
)
–
52
Motor Cooling System
Abnormality
Check the motor cooling system
Change the cooling system
Analog Temperature Sensor
Signal
Abnormality
Check if the analog temperature
feedback is fine
1. Check if the wiring is loose or
abnormal
2. Check if the parameters Pn-740,
Pn-741 are correct
Incorrect Motor Rated Current
Setting
Check the rated current value
Check the input parameters. Re-tune
if modifications are required.
Insufficient of Acc/Dec Time
Check the Acc/Dec parameters
Increase the Acc/Dec Time
Excessive Load
Check if the load rate continues
to exceed 100%
Replace the motor with one of greater
power
Users can observe the temperatures measured by KTY84 through status monitoring variables.
These variables correspond to the measured temperatures as follows:
Parameter
Parameter Descriptions
Pn-D60
Measured Temperature via KTY84 with Syntec Drive
Pn-D61
Measured Temperature via Feedback Syntec Encoder Internal KTY84
Pn-D62
Measured Temperature via Feedback Syntec Encoder External(1) KTY84
Pn-D63
Measured Temperature via Feedback Syntec Encoder External(2) KTY84
Pn-D64
Measured Temperature via Feedback Syntec Encoder External(3) KTY84
Pn-D65
Measured Temperature via 2nd Feedback Syntec Encoder Internal KTY84
Pn-D66
Measured Temperature via 2nd Feedback Syntec Encoder External(1)
KTY84