General use
Page 44/52
Installation, commissioning and operating instructions
SYCLOPE
TERE’O Touch
®
CU/PT
1)
Tank level
Pressing the « Tank level » button opens the programming window.
➢
Program the tank level :
If you are installing a tank level contact, it is necessary to
set its operating mode by pressing the corresponding mode.
➢
Stop dosing on tank low :
If this box is checked the dosage will be stopped when the
bottom of the tank is detected.
In the case where your regulator is connected on the
mysyclope site you can choose not to stop the dosing and to send
you an alarm email from the site.
Stop dosing option is not displayed if « Not used » mode is selected.
a)
Alarms
Pressing the « Alarms » button opens the programming window.
➢
Change low & high alarm :
Press the button corresponding to the value to be
modified to open the numeric keypad and enter the new alarm
threshold.
➢
Stop dosing on alarm :
If this checkbox is checked the dosage will be stopped
when an alarm is active.
Alarms are active only when your controller is in START mode and the polarization timer is not
active.
Settings
pH channel
Tank level
Selecting mode
Not used
Active - NO
Active - NC
Active
Stop dosing on tank low
Settings
pH channel
Alarms
High alarm
8.50
6.50
Active
Stop dosing on alarm
Low alarm