background image

  
 

Page | 27  

 

5.

 

Storage and Maintenance 

 

Operation 

The UPS system contains no user-serviceable parts. If the battery service life (3~5 years 
at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this 
case, please contact your dealer. 

 

 

 

 

 

Storage 

Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry 
location. During storage, recharge the battery in accordance with the following table: 

 

STORAGE TEMPERATURE 

RECHARGE FREQUENCY 

CHARGING DURATION 

 

-25°C - 40°C 

 

Every 3 months 

 

1-2 hours 

 

40°C - 45°C 

 

Every 2 months 

 

1-2 hours 

 

 

 

 

 

 

 

 

 

 

BE SURE TO DELIVER THE SPENT BATTERY TO A RECYCLING FACILITY OR SHIP IT 

TO YOUR DEALER IN THE REPLACEMENT BATTERY PACKING MATERIAL.

 

 

Summary of Contents for Contender 1 KVA

Page 1: ...USER MANUAL Online UPS Contender Series Rack Mount RM 120 VAC 220 VAC Capacity 1 KVA 1 5 KVA 2 KVA 3 KVA REVISION DESCRIPTION DATE Rev 1 3 Formal Release 2017 02 03...

Page 2: ...ll result in death or serious injury Warning Caution Unsafe practices that could endanger health safety and cause financial damage Important Any important technical and operating information on the eq...

Page 3: ...Install the UPS 6 2 3 Setup the UPS 7 2 4 Battery Replacement 10 2 5 Battery Kit assembly 11 3 Operations 14 3 1 Button Operation 14 3 2 LCD Panel 15 3 3 Audible Alarm 16 3 4 LCD display wordings inde...

Page 4: ...ATE THE ENVIRONMENT o Do not install the UPS system near water or in moist environments o Do not install the UPS system where it would be exposed to direct sunlight or near heater o Do not block venti...

Page 5: ...AGES REPAIRS MAY BE CARRIED OUT ONLY BY QUALIFIED MAINTENANCE PERSONNEL o Caution Risk of electric shock Even after the unit is disconnected from the mains commercial power components inside the UPS s...

Page 6: ...hen changing batteries install the same number and same type of batteries o Do not attempt to dispose of batteries by burning them This could cause battery explosion o Do not open or destroy batteries...

Page 7: ...ackage in a safe place for future use There are two different types of connector for the UPS In and Out online Please see the following model table 2 1 Rear Panel View Description UPS Programmable out...

Page 8: ...els Output circuit breaker 2 2 Install the UPS For safety consideration the UPS is shipped out from factory without connecting battery wires Before install the UPS please follow below steps to re conn...

Page 9: ...d door Maintain minimum clearance of 100mm in the bottom of the UPS to avoid dust and high temperature 2 Maintain an ambient temperature range of 0 C to 45 C for UPS optimal operation For every 5 C ab...

Page 10: ...on of breaker voltage 1 25 x battery voltage set current 50A Please choose battery size and connected numbers according to backup time requirement and UPS specifications To extend battery lifecycle it...

Page 11: ...OUT Connect a single modem phone fax line into surge protected IN outlet on the back panel of the UPS unit Connect from OUT outlet to the equipment with another modem fax phone line cable Step 5 Disab...

Page 12: ...ng the CD please execute setup exe file for initiating software installation 2 Follow the on screen instructions to install the software 3 When your computer restarts the monitoring software will appe...

Page 13: ...age 11 2 5 Battery kit Assembly OPTIONAL NOTICE Please assemble battery kit first before installing it inside of UPS Please select correct battery kit procedure below to assemble it Battery Kit 2 Unit...

Page 14: ...Page 12 Battery Kit 3 Units Battery Kit 4 Units...

Page 15: ...Page 13 Battery Kit 6 Units...

Page 16: ...on o Confirm selection key Press this button to confirm selection in UPS setting mode Select Button o Switch LCD message Press this button to change the LCD message for input voltage input frequency b...

Page 17: ...listed in details in section 3 7 and 3 8 Mute operation Indicates that the UPS alarm is disabled Output information Indicates the output voltage and output frequency Vac AC voltage Vdc DC voltage Hz...

Page 18: ...evel and low battery voltage Input battery voltage information Indicate the input voltage input frequency and battery voltage Vac AC voltage Vdc DC voltage Hz frequency 3 3 Audible Alarm Battery Mode...

Page 19: ...utput voltage For 200 208 220 230 240 VAC models you may choose the following output voltage 200 presents output voltage is 200Vac 208 presents output voltage is 208Vac 220 presents output voltage is...

Page 20: ...frequency is 50Hz BAT 60 presents output frequency is 60Hz If converter mode enable you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequenc...

Page 21: ...For 200 208 220 230 240 VAC models the setting range is from 7V to 24V of the nominal voltage Default 12V For 100 110 115 120 127 VAC models the setting range is from 3V to 12V of the nominal voltage...

Page 22: ...Parameter 1 2 Set the acceptable high frequency point and acceptable low frequency point for Bypass mode By pressing the Down key or Up key HLS Bypass high frequency point For 50Hz output frequency m...

Page 23: ...battery mode Default 999 12 Autonomy limitation setting INTERFACE SETTING Parameter 2 Set up backup time on battery mode for general outlets 0 999 setting the backup time in minutes from 0 999 for gen...

Page 24: ...ions are 1 2 4 6 8 1 2 4 6 8 setting the charger maximum current 1 2 4 6 8 in Ampere Default 8A 15 Charger Boost voltage setting INTERFACE SETTING Parameter 2 Set up the charger boost voltage 225 240...

Page 25: ...When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input voltage is...

Page 26: ...ring fault Sounding every 2 seconds EPO enable Sounding every 2 seconds Over temperature Sounding every 2 seconds Charger failure Sounding every 2 seconds Battery fault Sounding every 2 seconds At thi...

Page 27: ...ternal battery is incorrectly connected Check if all batteries are connected well Fault code is shown as 27 and the icon LCD display and alarm is continuously sounding Battery voltage is too high or t...

Page 28: ...fault has occurred There are two possible results 1 The load is still supplied but directly from AC power via bypass 2 The load is no longer supplied by power Contact your dealer Battery backup time...

Page 29: ...dealer Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table STORAGE TEMPERA...

Page 30: ...or 47 53 Hz Transfer Time Battery Mode Standard Model 4 hours recover to 90 capacity 1 5 A 2 Charging Voltage 27 4 VDC 1 41 1 VDC 1 82 1 VDC 1 41 1 VDC 1 54 8 VDC 1 82 1 VDC 1 LCD Display UPS status L...

Page 31: ......

Reviews: