Page | 20
230Vac to 264Vac (Default: 264Vac).
For
100/110/115/120/127 VAC
models:
120-140: setting the high voltage point from
115Vac to 132Vac (Default: 132Vac).
LLS: Bypass low voltage point.
For
200/208/220/230/240 VAC
models:
170-220: setting the low voltage point from
170Vac to 220Vac (Default: 170Vac).
For
100/110/115/120/127 VAC
models:
85-115: setting the high voltage point from
85Vac to 115Vac (Default: 85Vac).
09:
Bypass frequency range setting.
INTERFACE
SETTING
Parameter 1 & 2: Set the acceptable high
frequency point and acceptable low frequency
point for Bypass mode.
By pressing the Down key or Up key.
HLS: Bypass high frequency point
For
50Hz output frequency
models:
51-55Hz:
setting the frequency high loss point
from 51Hz to 55HZ
(Default: 53.0Hz)
For
60Hz output frequency
models:
61-65Hz:
setting the frequency high loss point
from 61Hz to 65Hz
(Default: 63.0Hz)
LLS: Bypass low Frequency point
For
50Hz output frequency
models:
45-49Hz:
setting the frequency low loss point
from
45Hz to 49HZ
(Default: 47.0Hz)
For
60Hz output frequency
models:
55-59Hz:
setting the frequency low loss point from
55Hz to 59Hz
(Default: 57.0Hz)