Page | 21
10:
Programmable outlets enable/disable
INTERFACE
SETTING
Parameter 2: Enable or disable programmable
outlets.
ENA:
Programmable outlets
enable.
DIS: Programmable outlets disable (Default)
11:
Programmable outlets setting
INTERFACE
SETTING
Parameter 2: Set up backup time limits for
programmable outlets.
0-999:
setting the backup time limits in minutes
from 0-999
for programmable outlets which
connect to non-critical devices on battery mode.
(Default: 999)
12:
Autonomy limitation setting
INTERFACE
SETTING
Parameter 2: Set up backup time on battery mode for
general outlets.
0-999:
setting the backup time in minutes
from 0-
999
for general outlets on battery mode.
DIS:
Disable the autonomy limitation and the
backup time will depend on battery
capacity. (Default)
NOTE:
When
setting as “0”, the backup time
will be
only
10 seconds
.
13:
Battery total AH setting
INTERFACE
SETTING
Parameter 2: Set up the battery total AH of the UPS.
7-999:
setting the battery total capacity from 7-999
in AH.
Please set the correct battery total capacity if external
battery bank is connected.