![Surefire BMS-350 Installation And Operation Manual Download Page 52](http://html1.mh-extra.com/html/surefire/bms-350/bms-350_installation-and-operation-manual_1406932052.webp)
52
MODBUS
INFORMATION
Time
step
Master's action
BMS-350 action
Registers
26
Polls command status register.
Sees OK (0x01). Proceeds to
next step.
40010 (status) 0x01
40011 (cmd) 0x04
40012 (param) 0x7D
40013 (exec) 0x01
27
Write 0x00 to command exec
reg.
40010 (status) 0x01
40011 (cmd) 0x04
40012 (param) 0x7D
40013 (exec) 0x00
28
Sees command exec register with
zero value. Returns to idle state.
40010 (status) 0x55
40011 (cmd) 0x04
40012 (param) 0x7D
40013 (exec) 0x00
29
Polls command status register.
Sees IDLE (0x55). All done!
40010 (status) 0x55
40011 (cmd) 0x04
40012 (param) 0x7D
40013 (exec) 0x00
6.0 DIP switch configuration and settings
Switch SW1 on the Modbus board configures the Modbus address, baud rate, and selects the serial interface to
be used. The notation “ON” and “OFF” follows from the direction of the arrow and the word “ON” located on
the left side of the switch body near SW1-1. The switches are as follows:
Make sure at the receiving end, the following bits are set as:
Data Bit = 8
Parity Bit = None
Stop Bit = 1
Switch
Selects
Description
SW1-1
Modbus address bit 0
“ON” position is “1”, “OFF” is 0
SW1-2
Modbus address bit 1
“ON” position is “1”, “OFF” is 0
SW1-3
Modbus address bit 2
“ON” position is “1”, “OFF” is 0
SW1-4
Modbus address bit 3
“ON” position is “1”, “OFF” is 0
SW1-5
Modbus address bit 4
“ON” position is “1”, “OFF” is 0
SW1-6
Baud rate for communication with Modbus master “ON” is 19200, “OFF” is 9600
SW1-7
Unused
Unused
SW1-8
Interface for communication with Modbus master “ON” is RS232, “OFF” is RS485
Summary of Contents for BMS-350
Page 1: ...Proudly Made in the USA BMS 350 Installation and Operations Manual...
Page 18: ...18 INSTALLATION WIRING DIAGRAM...
Page 19: ...19 FUEL TRAIN DIAGRAMS Piloted Fuel Train Pilotless Fuel Train...
Page 29: ...29 INTERMITTENT PILOT OPERATION Flow Chart...
Page 31: ...31 STANDING PILOT OPERATION Flow Chart...