TROUBLESHOOTING
GUIDE
Code Symptom
Action
Visual
22
Stage 1 solenoid
valve
disconnected
Pilot/Main burner
not running.
No activity when
attempting startup.
1. System detecting a disconnect upon
initial start-up.
2. Check device for faulty operation.
3. Verify wiring from device.
4. System detecting battery volts below
12V.
5. Verify battery voltage.
Blinking Red LED.
23
T/C High Temp
Shutdown
Pilot/Main burner
not running.
No activity when
attempting startup.
Ports 15 and 16
are activated.
1. System detecting a disconnect upon
initial start-up.
2. Check device for faulty operation.
3. Verify wiring from device.
4. Jumper is required if function is not be-
ing utilized.
5. Verify jumper is installed.
Blinking Red LED.