![Surefire BMS-350 Installation And Operation Manual Download Page 39](http://html1.mh-extra.com/html/surefire/bms-350/bms-350_installation-and-operation-manual_1406932039.webp)
39
TROUBLESHOOTING
GUIDE
SHUTDOWN CODES Cont.
Code Symptom
Action
Visual
18
Extreme High
Temp
Pilot/Main burner
not running.
No activity when
attempting startup.
1. Process temperature has exceed EHTD
setting.
2. Inspect for leaking control valves.
3. Solenoid valve not closing.
Blinking Red LED
19
Shutdown
Interlock
Pilot/Main burner
not running.
No activity when
attempting startup.
Ports 24 and 25
are activated.
1. System detecting an open
circuit upon initial start-up.
2. Customer supplied switch is activated.
3. Check switching device for faulty oper-
ation.
4. Verify wiring from switching device.
5. Verify jumper is installed.
6. Jumper is required if function is not be-
ing utilized
Blinking Red LED
20
Main Fuel
Valve Failure
Pilot/Main burner
not running.
No activity when
attempting startup.
Ports 26 and 27
are activated.
1. System detecting an open circuit upon
initial start-up.
2. Customer supplied switch on main
burner control valve has detected an
unsafe condition.
2. Customer supplied switch is activated.
3. Check switching device for faulty oper-
ation.
4. Verify wiring from switching device.
5. Verify jumper is installed.
6. Jumper is required if function is not be-
ing utilized
7. DO NOT USE AS SHUTDOWN.
Blinking Red LED
21
Replace FT
Ignition Unit
Pilot/Main burner
not running.
No activity when
attempting startup.
1. Igniter Ohms exceeded 4 Ohms
2. Igniter has deteriorated causing high
ohms.
Blinking Red LED.
Summary of Contents for BMS-350
Page 1: ...Proudly Made in the USA BMS 350 Installation and Operations Manual...
Page 18: ...18 INSTALLATION WIRING DIAGRAM...
Page 19: ...19 FUEL TRAIN DIAGRAMS Piloted Fuel Train Pilotless Fuel Train...
Page 29: ...29 INTERMITTENT PILOT OPERATION Flow Chart...
Page 31: ...31 STANDING PILOT OPERATION Flow Chart...