Function:
Parameters:
RTD High Temp
34
°
F — 590
°
F
TC Low Temp
32
°
F — 2398
°
F
TC High Temp
34
°
F — 2400
°
F
Safety Thermocouple
40
°
F — 2400
°
F
FPT (Flame Proof Timing)
15 seconds — 60 seconds
Solenoid Timing
5 seconds — 60 seconds
EHTD
10
°
F — 1000
°
F
Set Point Parameters
RTD Low Temp
32
°
F — 588
°
F
Operational Situations
Operational State
Alarm
Run Status
Red LED
Green
LED
Blue LED
Amber LED
System OFF or Manual
Shutdown
Open
Open
ON
OFF
OFF
OFF
System ON, Pre-purge
complete, Igniter On
Close
Open
OFF
ON
OFF
ON
Flame sensed, Burner run-
ning No Errors
Close
Close
OFF
ON
ON
OFF
Shutdown, Igniter Error
Open
Open
Blinking
OFF
OFF
Blinking
Stand By Error
Close
Open
OFF
Blinking
OFF
OFF
Shutdown Interlock
Open
Open
Blinking
OFF
OFF
OFF