26
OPERATIONS
GUIDE
Status Codes
Run Codes
Description
00
System running, no errors
01
Waiting for startup signal
02
Pre-purge on Startup
07
Purge between Ignition Attempts
08
Waiting for stage 2 solenoid valve to open
Standby Codes
Description
09
Standby Interloop
10
Loss of Fuel Gas
Shutdown Error Codes
Description
11
Manual Shut Off
12
Max Retries Exceeded
13
Low Battery Volts
The low voltage cut off for the system is @ 10.6 Volts
14
Igniter Short Circuit
15
Igniter Open Circuit
16
Flame Sensed Before Startup, FR Short
17
RTD or T/C Error or Disconnected
Temp for RTD < 1
°
F or > 655
°
F
Temp for TC > 2650
°
F
18
Extreme High Temp
19
Shutdown Interlock
20
Main Fuel Valve Failure
21
Replace FT-Ignition Unit
22
Stage 1 Solenoid Disconnected
23
T/C High Temp Shutdown