COMPONENT
DESCRIPTION
SureFire FT-Series Ignition Units
The SureFire BMS-350 is compatible with most FT series
igniters. Each unit is designed for specific applications.
Piloted System
FT-1 System are designed for long life in burner
applications as a pilot. The FT-1 series offers
flame sensing through flame rod or thermocouple.
NOTE: Please consult local SureFire Field Tech Support
for proper pilot placement and proper orifice sizing selec-
tion.
FT-1-SF (above)
These unit above is utilizing a Flame Rod as
a flame sensing mechanism.
Optional Flame Sensors
Flame Rod
Nichrome flame rod rated to 2600°F
Armored wiring harness rated to 1000°F duty / 1500°F
flash
Enclosed fire tube service
Direct termination to BMS-350 controller
Thermocouple
Type K thermocouple flame sensing rated to 2400°F
Armored wiring harness rated to 1000°F duty / 1500°F
flash
Exposed combustor or incinerator service
Direct termination to the BMS-350 controller
FT-1-ST (above)
These unit above is utilizing a Thermocouple
as a flame sensing mechanism.