Premier VS Infrared Heating System
Page 48
June 04, 2014
INSTALLATION -
Part 2
B
- Ventilation Connections
1.
Install Ventilation system pipes, etc. as per design / conformance with required Codes and connect with
Vacuum Pump Outlet. Ensure that there is a minimum of 2” (5 cm) between the Vacuum Pump outlet and
the first rigid section of the Ventilation piping to avoid mechanical contact between the two. Use the
Silicone Connector Boot to connect the Vent Pipe to the Vacuum Pump Outlet.
(Refer to Figure 33 or Figure 34 respectively for mounting type details.)
Fasten To Ceiling Bolts
Approved Thimble
(If Necessary)
Flashing
Rain Cap
Air
Fl
ow
Di
rec
tio
n
FOR VERTICAL VENTING REFER
TO ANSI Z223.1 AND CAN/CGA B149.1
AND B149.2 FOR FAN ASSISTED
APPLIANCES.
Figure 33: Side Wall Mounting - Recommended Venting (Horizontal)
Figure 34: Ceiling Mounting - Recommended Venting (Vertical)
Approved wall thimble
(if necessary)
4" Ø: CS006
6" Ø: CS033
Vent Terminal
4" Ø: CT011
6" Ø: CT044
18" Min.
24"-26"
Preferred
Air
Fl
ow
Di
rec
tio
n