background image

 

9

 
7.0. 

MAINTENANCE 

To  ensure  maximum  life  of  the  equipment,  the 
following  should  be  part  of  an 

annual 

maintenance 

program. 
 

Warning 
De-energize  unit  before  performing  maintenance. 
Voltages  are  present  inside  this  unit  which  can 
cause injury. Therefore, only personnel qualified to 
service  electrical  equipment  should  perform 
maintenance on this unit. 

 

7.1. 

Vacuum  the  voltage  regulator  inside  and  out  to 

remove  accumulated  dirt,  which  could  lead  to 
overheating or insulation failure. 
 

7.2. 

Tighten  all  electrical  connections,  particularly  all 

power wiring to, and in, the unit. 
 

7.3. 

Inspect  all  variable  transformer  brushes  and 

commutators  for  signs  of  wear  or  pitting.  Replace  as 
required. See diagram below. 
 

 

 

Do  not  attempt  to  clean  a  commutator  with  an 
abrasive  such  as  sandpaper  or  a  file. 

This  will  ruin 

the  soft  precious  metal  plating  on  the  commutator  and 
will  shorten  the  life  of  the  unit.  It  is  normal  for 
commutators  to  become  black  due  to  carbon  brush 
tracking.  If  a  commutator  is  to  be  cleaned,  use 
denatured alcohol and a soft cloth. 
 

7.4. 

Inspect  the  variable  transformer  drive  belts, 

sprockets,  gears,  cams,  etc.  for  signs  of  slippage  or 
wear and adjust as required. 
 

7.5. 

Check  the  variable  transformer  radiator(s)  (the 

die cast part that holds the brush assembly) for signs of 
slippage,  and  see  if  all  brushes  driven  by  the  same 
motor are aligned with each other. The alignment of the 
radiator  and  brushes  depends  on  the  setscrews  that 
hold the variable transformer center tube(s) to the shaft 
and  the  setscrews  that  hold  the  radiator  to  the  center 
tube. Adjust and tighten as needed. 
 

7.6. 

Lubrication  of  the  WHR  Series voltage regulator 

is  not  required  since  it  has  been  lubricated  at  the 
factory for its lifetime. 
 

8.0. 

TROUBLESHOOTING 

WHR  Series  voltage  regulators  will  provide  long, 
reliable  service  with  little  attention.  Unless  the  unit  is 
overloaded,  there  is  little  likelihood  of  component 
failure. 
 

Warning 
Voltages  are  present  inside  this  unit  which  can 
cause injury. Therefore, only personnel qualified to 
service  electrical  equipment  should  perform 
trouble-shooting procedures on this unit. 

 
If  the  regulator  fails  to  operate  correctly,  the  following 
checks  will  help  locate  and  correct  the  problem.  Refer 
to the schematic, rating chart and replacement parts list 
for further information. 
 

8.1. 

Check  the  load  connected  to  the  voltage 

regulator  to  be  sure  the  unit's  output  current  rating  is 
not being exceeded. 
 

8.2. 

See  if the POWER pilot lamps are on. If a lamp 

is not on, there is no power to the voltage regulator, or 
control  module  fuses  F1  and  F2  (POWER  fuses)  are 
blown, or the lamp has burned out. Check the POWER 
fuses (F1 and F2). Check the power input to the unit to 
be sure the voltage is within the range specified for the 
selected output voltage. 
 

8.3. 

Check  the  output  voltmeters.  If  a  meter  shows 

zero  output  voltage,  check  the  input  line,  control 
module  fuses  F3  and  F4  (CONTROL  fuses),  remote 
sense  wiring  if  applicable,  and  input  connections.  If  so 
equipped,  check  position  of  input  circuit  breaker  and 
manual bypass switch. 
 

8.4. 

Check  the  CONTROL  pilot  lamps.  If  one  is  not 

lit,  check  it's  VOLTAGE  RANGE  switch  to be sure it is 
on  and  check  for  blown  CONTROL  fuses  (F3 and F4). 
If applicable, check the remote sense wiring. 
 

8.5. 

If the motor hunts (cycles continuously), readjust 

the SENSITIVITY control. 
 

8.6. 

If  a  motor  drives  a  POWERSTAT  variable 

transformer  to  one  end  of  its  travel,  and  the  voltage 
decreases when it should increase or increases when it 
should  decrease,  check  to  see  if  the  input  and  output 
power  connections  to  the  voltage  regulator  are 
reversed. If applicable, check the remote sense wiring. 
 

8.7. 

If  the  unit  has  been  reworked or repaired, check 

to  see  if  the  leads  driving  the  motor  have  been 
reversed.  A1-TB1-2  and  A1-TB1-3  provide  the  motor 
power to lower and raise the motor with A1-TB1-1 being 
the common for both AC voltages.  
 

Summary of Contents for STABILINE WHR22 Series

Page 1: ...to make engineering changes on all its products Such refinements may affect information given in the instructions Therefore USE ONLY THE INSTRUCTIONS THAT ARE PACKED WITH THE PRODUCT WARNING High vol...

Page 2: ...xamine it carefully for any shipping damage The Damage and Shortage instructions packed with the unit outlines the procedure to follow if any parts are missing or damaged 2 0 DESCRIPTION 2 1 GENERAL W...

Page 3: ...nge S Single Control D Double Control T Triple Control LNN Size Code 3 or 4 digits R Rack Cabinet T Tall Cabinet CB Input Circuit Breaker CS Input Circuit Breaker w 120vac Shunt Trip CR Input Circuit...

Page 4: ...mum rated current as specified by local and national code requirements The front panel s of the voltage regulator must be removed to allow access to the input and load terminals To remove a panel use...

Page 5: ...5 2 SETTING OUTPUT VOLTAGE AND SENSITIVITY POTENTIOMETERS Normally the WHR Series voltage regulator should not be operated without the front panel s of the cabinet in place However during the initial...

Page 6: ...eaker if the coil voltage is lost The trip coil is rated 120 volt AC The coil voltage must be present in order to close the circuit breaker 6 2 1 3 Circuit Breaker Trip Coil Alarm Contacts When alarm...

Page 7: ...ged the factory settings and did not select the store option the factory setting can be reinstated by pressing both RECALL buttons at the same time The stored factory settings are shown in the table b...

Page 8: ...ted load current and in some cases the maximum rated nominal input voltage must be reduced Refer to the All Buck and All Boost Rating Chart for the all boost ratings For all boost operation the input...

Page 9: ...ess the unit is overloaded there is little likelihood of component failure Warning Voltages are present inside this unit which can cause injury Therefore only personnel qualified to service electrical...

Page 10: ...e motor at the end of travel If the motor operates successfully in this test the problem may be with the control board 8 10 Inspect the POWERSTAT Variable Transformer brush s and commutator s for sign...

Page 11: ...F38 850 200 1200 INPUT VOLTAGE 240 120 FREQUENCY 50 60 Hz CONNECTION 1 Phase 3 Wire RANGE 20 to 10 of Selected Output OUTPUT VOLTAGE 240 120 CONNECTION 50 60 HZ Model Number base unit Rated Load Max I...

Page 12: ...ilated enclosures intended for indoor use under usual service conditions Temperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to...

Page 13: ...ONTROL MODULE ASSEMBLY A1 Standard Reference Symbol Part Description Part Number A1 CONTROL MODULE 213243 002 A1 A1 CONTROL BOARD 227412 001 A1 F1 F2 F3 F4 FUSE 600V 104364 003 A1 LP1 LP2 LIGHT INDICA...

Page 14: ...n 10 5 AUX POWER MODULE There is one standard power module used throughout this WHR Series of STABILINE Automatic Voltage Regulators It is used for Line to Line connections Line Line Reference Symbol...

Page 15: ...15 11 0 SCHEMATIC For reference only use full size supplied with unit...

Page 16: ...16 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters...

Page 17: ...17 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 19: ...19 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters...

Page 20: ...20 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters...

Page 21: ...21 Enclosures DD through GG Note All dimensions are inches millimeters...

Page 22: ...22 Enclosures DD through GG continues Note All dimensions are inches millimeters...

Page 23: ...23 Enclosures EEE through GGG Note All dimensions are inches millimeters...

Page 24: ...24 Enclosures EEE through GGG continues Note All dimensions are inches millimeters...

Page 25: ...25 13 0 RACK MOUNT DIMENSIONS OPEN Enclosures R1 and R2 Note All dimensions are inches millimeters...

Page 26: ...hich offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are availab...

Reviews: