5

5.0. 

OPERATION 

 

5.1.  CONTROL MODULE ASSEMBLY 
 
5.1.1. 

General 

The  control  modules  contain  the  circuitry  that  senses 
the  output  voltage  and  determine  if  correction  is 
needed. When correction is required this circuit sends a 
raise  or  lower  signal  to  the  motor  driven  variable 
transformers.  To  eliminate  unauthorized  tampering  of 
the  control  module  the  items  marked  (

)  below  are 

located behind the front panel. 
 

5.1.2. 

Power Pilot Lamps

  (A1-LP1)

 

The  POWER  lamp  on  each  control  assembly  lights 
when power is present for the motor on that phase. This 
indicates the voltage regulator is energized. 
 

5.1.3. 

Control Pilot Lamps  (

A1-LP2)

 

The  CONTROL  lamp  lights  when  the control assembly 
sense  voltage  for  that  phase  is  energized.  The  control 
sense  voltage  must  be  energized  for  automatic 
correction of voltage changes to occur. 
 

5.1.4. 

Analog Voltmeters

  (A1-M1)

 

These  meters  show  the  output  voltages.  There  is  one 
meter  for  each  phase.  They  sense  line-to-neutral 
voltage,  and  display  line-to-neutral  voltage  and  the 
equivalent line to line voltage. 
 

5.1.5. 

Output Voltage Range Toggle Switches

 

(A1-S1)

 

With  these  switches  in  the  OFF  position,  the  control 
sense  voltage  for  that  phase  is  disconnected  and  the 
control  pilot  lamp  is  not  illuminated.  In  this  position 
automatic correction for voltage changes on that phase 
will not take place and any change in input voltage will 
be  reflected  in  output  voltage.  The  switches  (one  for 
each  phase)  should  be  placed  in  either the “380Y/220” 
or “480Y/277” position to energize the control assembly 
sense voltage and allow automatic correction of voltage 
changes.  
 

5.1.6. 

Output Voltage Potentiometers 

 

These  potentiometers  set  the  line  to  neutral  output 
voltages, one for each phase. The adjustment range is 
approximately  ±  10%  of  selected  nominal  output 
voltage. 
 

5.1.7. 

Sensitivity Potentiometers 

 

These  potentiometers  adjust  the  voltage  regulator’s 
output accuracy and therefore set how much the output 
voltage will change before the unit will correct. There is 
a SENSITIVITY potentiometer for each sensed phase. 
 

5.1.8. 

Fuses

 (A1-F1 to A1-F4) 

 

The  four  fuses  located  on  the  control  module  protect 
the  motor  and  sense  power  lines.  If  the  POWER  or 
CONTROL lights are not lit, and all control settings are 
proper, check for a blown fuse. 

5.2.  SETTING OUTPUT VOLTAGE AND 

SENSITIVITY POTENTIOMETERS 

Normally, the WHR Series voltage regulator should not 
be  operated  without  the front panel(s) of the cabinet in 
place.  However,  during  the  initial  operation  of  the 
regulator,  the  front  panels  can  be  removed  to  allow 
setting  the  OUTPUT  VOLTAGE  and  SENSITIVITY 
potentiometers. 
 

5.2.1. 

Energize Regulator 

On units equipped with a manual bypass switch ensure 
it  is  in  the  REGULATOR  position.  Energize  the 
regulator  power  source  and  place  the  input  circuit 
breaker,  if  so  equipped,  in  the  "ON"  position.  The pilot 
lamps should light, indicating that the voltage regulator 
is  energized  and  that  the  control  unit  is  on.  If 
necessary,  move  the  OUTPUT  VOLTAGE  RANGE 
switch  on  each  phase  to  the  desired  nominal  output 
voltage position. The voltmeters will indicate the output 
voltages. 
 

5.2.2. 

Set Output 

To  adjust  the  output  voltage  on  any  phase,  turn  the 
OUTPUT  VOLTAGE  potentiometer  clockwise  to 
increase  or  counterclockwise  to  decrease  the  output 
voltage, as indicated on the voltmeter for that phase. 
 

5.2.3. 

Set Sensitivity 

The sensitivity must be adjusted if the voltage regulator 
hunts  (any  of  the  motor  driven  variable  transformer 
sections  of  the  regulator  continually  cycles  back  and 
forth) or if the regulator allows too great a change from 
the set voltage before correction occurs. 
 
Turning  the  SENSITIVITY  control  clockwise  increases 
the  sensitivity  to  maximum  (±0.75%  to  ±1%  output 
voltage  accuracy).  For  maximum  sensitivity,  turn  the 
SENSITIVITY  control  on  one  phase  clockwise  to  the 
point where the POWERSTAT on that phase begins to 
hunt. Turn the control counterclockwise (CCW) until the 
hunting  stops.  Turn  the  control  an  additional  1/4  turn 
CCW. Repeat for the other two phases. 
 

5.2.4. 

Close

 

Replace the front cover(s). 
 

5.3.  REMOTE SENSING 

Normally,  these  voltage  regulators  sense  and  regulate 
each  line  to  neutral  voltage  at  the  regulator's  output 
terminals, In some cases better control can be obtained 
by  regulating  the  voltage  at  another  point,  such  as  at 
the  end  of  long  lines  between  the  regulator  and  the 
load. This is known as remote sensing. 
 
If  remote  sensing  is  desired,  move  the  wire  connected 
to  terminal  6  to  terminal  7  and  the  wire  connected  to 
terminal  8  to  terminal  9  on  each  control  module 
terminal  panel.  This  will  disconnect  the  control module 
sense  terminals  from  the  output  terminals  of  the 
regulator. Connect remote sensing wires to terminals 6 
and 8 on the control modules. 

Summary of Contents for STABILINE WHR22 Series

Page 1: ...to make engineering changes on all its products Such refinements may affect information given in the instructions Therefore USE ONLY THE INSTRUCTIONS THAT ARE PACKED WITH THE PRODUCT WARNING High vol...

Page 2: ...xamine it carefully for any shipping damage The Damage and Shortage instructions packed with the unit outlines the procedure to follow if any parts are missing or damaged 2 0 DESCRIPTION 2 1 GENERAL W...

Page 3: ...nge S Single Control D Double Control T Triple Control LNN Size Code 3 or 4 digits R Rack Cabinet T Tall Cabinet CB Input Circuit Breaker CS Input Circuit Breaker w 120vac Shunt Trip CR Input Circuit...

Page 4: ...mum rated current as specified by local and national code requirements The front panel s of the voltage regulator must be removed to allow access to the input and load terminals To remove a panel use...

Page 5: ...5 2 SETTING OUTPUT VOLTAGE AND SENSITIVITY POTENTIOMETERS Normally the WHR Series voltage regulator should not be operated without the front panel s of the cabinet in place However during the initial...

Page 6: ...eaker if the coil voltage is lost The trip coil is rated 120 volt AC The coil voltage must be present in order to close the circuit breaker 6 2 1 3 Circuit Breaker Trip Coil Alarm Contacts When alarm...

Page 7: ...ged the factory settings and did not select the store option the factory setting can be reinstated by pressing both RECALL buttons at the same time The stored factory settings are shown in the table b...

Page 8: ...ted load current and in some cases the maximum rated nominal input voltage must be reduced Refer to the All Buck and All Boost Rating Chart for the all boost ratings For all boost operation the input...

Page 9: ...ess the unit is overloaded there is little likelihood of component failure Warning Voltages are present inside this unit which can cause injury Therefore only personnel qualified to service electrical...

Page 10: ...e motor at the end of travel If the motor operates successfully in this test the problem may be with the control board 8 10 Inspect the POWERSTAT Variable Transformer brush s and commutator s for sign...

Page 11: ...F38 850 200 1200 INPUT VOLTAGE 240 120 FREQUENCY 50 60 Hz CONNECTION 1 Phase 3 Wire RANGE 20 to 10 of Selected Output OUTPUT VOLTAGE 240 120 CONNECTION 50 60 HZ Model Number base unit Rated Load Max I...

Page 12: ...ilated enclosures intended for indoor use under usual service conditions Temperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to...

Page 13: ...ONTROL MODULE ASSEMBLY A1 Standard Reference Symbol Part Description Part Number A1 CONTROL MODULE 213243 002 A1 A1 CONTROL BOARD 227412 001 A1 F1 F2 F3 F4 FUSE 600V 104364 003 A1 LP1 LP2 LIGHT INDICA...

Page 14: ...n 10 5 AUX POWER MODULE There is one standard power module used throughout this WHR Series of STABILINE Automatic Voltage Regulators It is used for Line to Line connections Line Line Reference Symbol...

Page 15: ...15 11 0 SCHEMATIC For reference only use full size supplied with unit...

Page 16: ...16 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters...

Page 17: ...17 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 19: ...19 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters...

Page 20: ...20 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters...

Page 21: ...21 Enclosures DD through GG Note All dimensions are inches millimeters...

Page 22: ...22 Enclosures DD through GG continues Note All dimensions are inches millimeters...

Page 23: ...23 Enclosures EEE through GGG Note All dimensions are inches millimeters...

Page 24: ...24 Enclosures EEE through GGG continues Note All dimensions are inches millimeters...

Page 25: ...25 13 0 RACK MOUNT DIMENSIONS OPEN Enclosures R1 and R2 Note All dimensions are inches millimeters...

Page 26: ...hich offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are availab...

Reviews: