background image

 

8

6.2.8. 

Soft Start 

The  soft  start  option  controls  the  WHR  Series  Voltage 
Regulator so that when power is applied the regulator’s 
output  voltage  starts  out  approximately  10%  low  and 
after  a  preset  time  delay,  the  output  voltage  ramps  up 
to the selected regulated output voltage.  
 
When  input  power  is  lost,  the  soft  start  controls 
automatically 

drives 

the 

POWERSTAT 

power 

module(s) to the minimum output voltage position using 
the  output  power  from  a  small  uninterruptible  power 
supply  (UPS).  The  UPS  then  turns  off  automatically. 
For UPS care and maintenance see the UPS manual. 
 
When regulator power is restored, the load voltage will 
be  approximately  7%  less  than  the  input  voltage  on 
narrow  range  WHR  Regulators  and  13%  less  than  the 
input  voltage  on wide range models. After a short time 
delay,  the  regulator  output  voltage  ramps  up  to  the 
selected, regulated output voltage. 
 

6.3.  ALL-BUCK AND ALL-BOOST OPERATION 

All WHR Series regulators can be connected to provide 
all-buck  (unit  will  only  lower  the  input  voltage)  or 
all-boost  (unit  will  only  increase  the  input  voltage) 
operation. This feature can be used to shift the nominal 
voltage  or  to  correct  input  voltages  that  are  always 
extremely high or extremely low. 
 

6.3.1. 

4.4.1 All-Boost Operation 

When connected for all-boost, the units will bring extra 
low  voltages  up  to  nominal,  but  will  not  correct  high 
input  voltages.  Since  operation  in  the  all-boost  mode 
will  increase  the  voltage  and  heating  in  the  WHR 
regulator, the rated load current, and in some cases the 
maximum  rated  nominal  input  voltage,  must  be 
reduced.  Refer  to  the  “All  Buck  and  All  Boost  Rating 
Chart”  for  the  all-boost  ratings.  For  all-boost  operation 
the  input  line  to  each  POWERSTAT  variable 
transformer must be moved from terminal 2 to terminal 
5. 
 

6.3.2. 

4.4.2 All-Buck Operation 

When  connected  for  all-buck  operation,  the  units  will 
bring extra high input voltages down to nominal, but will 
not correct low input voltages. Since all-buck operation 
reduces  the  voltage  in  the  regulator,  the  nominal  input 
voltage  can  be  increased.  The  current  ratings  remain 
the  same.  Refer  to  the  “All  Buck  and  All  Boost  Rating 
Chart”  for  all-buck  ratings.  All-buck  operation  requires 
moving  the  input  line  to  each  POWERSTAT  Variable 
Transformer from terminal 2 to terminal 4. 
 
 

 
 

All Buck and All Boost Rating Chart 

Standard Rating 

All Buck Operation 

All Boost Operation 

(max output voltage = input voltage) 

(min output voltage = input voltage) 

 

 

Maximum 

Nominal 

Input Voltage 

§ 

Minimum 

Output 

Voltage 

(% of 

Input) 

† High 

Input 

Voltage 

Range 

(% of 

Output) 

Maximum 

Nominal 

Input Voltage 

§ 

Maximu

m Output 

Voltage 

(% of 

Input) 

‡ Low 

Input 

Voltage 

Range 

(% of 

Output) 

Current 

De-rating 

(% of 

rated) 

Voltage 

Range 

50 Hz 

60 Hz 

50 Hz 

60 Hz 

240 X 208 

Narrow 

277 

277 

80% 

125% 

208 

240 

125% 

75% 

77% 

Wide 

300 

300 

67% 

150% 

208 

240 

150% 

65% 

72% 

 

 

 

 

 

 

 

 

 

 

 

§ Selectable output voltage is a function of the control module and must remain within the limits specified in the unit rating charts. 

† In all buck operation the input voltage range is from the selected output voltage to the 'high input voltage range'. 

‡ In all boost operation the input voltage range is from the 'low input voltage range' to the selected output voltage. 

 

 

Summary of Contents for STABILINE WHR22 Series

Page 1: ...to make engineering changes on all its products Such refinements may affect information given in the instructions Therefore USE ONLY THE INSTRUCTIONS THAT ARE PACKED WITH THE PRODUCT WARNING High vol...

Page 2: ...xamine it carefully for any shipping damage The Damage and Shortage instructions packed with the unit outlines the procedure to follow if any parts are missing or damaged 2 0 DESCRIPTION 2 1 GENERAL W...

Page 3: ...nge S Single Control D Double Control T Triple Control LNN Size Code 3 or 4 digits R Rack Cabinet T Tall Cabinet CB Input Circuit Breaker CS Input Circuit Breaker w 120vac Shunt Trip CR Input Circuit...

Page 4: ...mum rated current as specified by local and national code requirements The front panel s of the voltage regulator must be removed to allow access to the input and load terminals To remove a panel use...

Page 5: ...5 2 SETTING OUTPUT VOLTAGE AND SENSITIVITY POTENTIOMETERS Normally the WHR Series voltage regulator should not be operated without the front panel s of the cabinet in place However during the initial...

Page 6: ...eaker if the coil voltage is lost The trip coil is rated 120 volt AC The coil voltage must be present in order to close the circuit breaker 6 2 1 3 Circuit Breaker Trip Coil Alarm Contacts When alarm...

Page 7: ...ged the factory settings and did not select the store option the factory setting can be reinstated by pressing both RECALL buttons at the same time The stored factory settings are shown in the table b...

Page 8: ...ted load current and in some cases the maximum rated nominal input voltage must be reduced Refer to the All Buck and All Boost Rating Chart for the all boost ratings For all boost operation the input...

Page 9: ...ess the unit is overloaded there is little likelihood of component failure Warning Voltages are present inside this unit which can cause injury Therefore only personnel qualified to service electrical...

Page 10: ...e motor at the end of travel If the motor operates successfully in this test the problem may be with the control board 8 10 Inspect the POWERSTAT Variable Transformer brush s and commutator s for sign...

Page 11: ...F38 850 200 1200 INPUT VOLTAGE 240 120 FREQUENCY 50 60 Hz CONNECTION 1 Phase 3 Wire RANGE 20 to 10 of Selected Output OUTPUT VOLTAGE 240 120 CONNECTION 50 60 HZ Model Number base unit Rated Load Max I...

Page 12: ...ilated enclosures intended for indoor use under usual service conditions Temperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to...

Page 13: ...ONTROL MODULE ASSEMBLY A1 Standard Reference Symbol Part Description Part Number A1 CONTROL MODULE 213243 002 A1 A1 CONTROL BOARD 227412 001 A1 F1 F2 F3 F4 FUSE 600V 104364 003 A1 LP1 LP2 LIGHT INDICA...

Page 14: ...n 10 5 AUX POWER MODULE There is one standard power module used throughout this WHR Series of STABILINE Automatic Voltage Regulators It is used for Line to Line connections Line Line Reference Symbol...

Page 15: ...15 11 0 SCHEMATIC For reference only use full size supplied with unit...

Page 16: ...16 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters...

Page 17: ...17 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 19: ...19 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters...

Page 20: ...20 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters...

Page 21: ...21 Enclosures DD through GG Note All dimensions are inches millimeters...

Page 22: ...22 Enclosures DD through GG continues Note All dimensions are inches millimeters...

Page 23: ...23 Enclosures EEE through GGG Note All dimensions are inches millimeters...

Page 24: ...24 Enclosures EEE through GGG continues Note All dimensions are inches millimeters...

Page 25: ...25 13 0 RACK MOUNT DIMENSIONS OPEN Enclosures R1 and R2 Note All dimensions are inches millimeters...

Page 26: ...hich offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are availab...

Reviews: