the  regulator  to  the  load.  In  the  BYPASS  position  the 
input  power  and  load  are  disconnected  from  the 
regulator’s circuits and connects together directly. THIS 
IS  A  NON-LOAD  BREAK  SWITCH  AND  INPUT 
POWER  MUST  BE  OFF  BEFORE  OPERATING.  On 
three phase units the neutral is not switched. 
 

Caution:

  This  switch  is  designed  to  provide 

unconditioned  power  to  the  load  if  a  fault  condition 
occurs. 

It  does  not  remove  all  live  power  from  the 

enclosure.

 The manual bypass switch does not bypass 

the input circuit breaker if so equipped. 
 

6.2.4. 

Ammeters

 (M1) 

An  analog  ammeter  displays  load  current  for  each 
phase. Each meter indicates the load current within 2% 
of the meters full range. 
 

6.2.5. 

Frequency meter with alarm contacts

 (M2) 

Frequency  meter  displays  the  source  frequency  and 
provides  alarm  contacts  for  values  outside  the  user's 
settable  limits.  Lower  and  upper  limit  trip  relays  are 
factory  set  at  45  Hz  and  65  Hz  respectively.  If  the 
frequency  becomes  lower  or  higher  than  user  selected 
values,  an  output  relay  is  energized.  The  relay  is 
equipped  with  a  form  “C”  normally  open  /  normally 
closed contact available for customer use. 
 
If  a  circuit  breaker  with  a  trip  coil  is  ordered  with  the 
frequency  meter,  the  system  is  configured  to 
automatically trip the breaker when a limit is exceeded. 
 

6.2.5.1.  Frequency

 

Meter Instructions

 

The  frequency  meter  owner’s  manual  is  included  with 
the  literature  sent  with  the  unit.  The  user  can  change 
the  meters  setting  without  storing  them  in  memory.  If 
the  user  changed  the  factory  settings,  and  did  not 
select  the  store  option,  the  factory  setting  can  be 
reinstated  by  pressing  both  RECALL  buttons  at  the 
same time. The stored factory settings are shown in the 
table below. 
 
To  return  the  stored  settings  to  the  factory  defaut,  tap 
the ENTER key to go to the next feature then use SET 
and  ADVANCE  keys  to  change  the  setting  to  those 
shown  below.  When  the  display  shows  Store,  tap  the 
Enter  key  to  lock  the  setting  into  memory.  If  no  other 
setting  was  stored  after  this  procedure,  pressing  both 
RECALL keys will return the meter to these settings. 

 

Feature 

Setting 

Func 

Freq 

 

Scale 

A / SC 

2.00000 

Offset 

000000. 

 

Range 

FFFF.FF 

 

Slope 

A Pos 

 

Sp lo 

000045 

 

Sp hi 

000065 

 

Gate t 

01.30 

 

Conf 1 

no setting required 

 

Conf 2 

no setting required 

 

No store 

Store 

 

 
A  front  and  rear  view  of  the  frequency  meter  is  shown 
below  with  the  N.O.  alarm  contacts  in  parallel.  The 
alarm contacts are connected to TB4 as follows: 
 

1 – HI relay Com 

 

4 - LO relay COM 

2 – HI relay N.O. 

 

5 - LO relay N.O. 

3 – HI relay N.C. 

 

6 - LO relay N.C. 

 

Frequency Meter 

 

 

 
6.2.6. 

Input Range Alarm

 (K1)

 

Input voltage range alarm closes a N.O. solid state 
contact when the regulator is providing maximum 
voltage correction.  This option senses regulator motor 
drive end of travel limit switch operation. 

 

Alarm circuit contacts provided with the Frequency Trip 
Meter  and  Input  Voltage  Range  Alarm  -  Phase 
Reversal options are rated 5 amps 240 volts AC. 
 

6.2.7. 

Manual Raise / Lower Switches

 (A1-S2 & 

A2-S3) 

Manual  raise  /  lower  switches allow the user to disable 
the  automatic  control  unit  and  manually  raise  or  lower 
the  output  voltage  using  the  motor  drive.    The 
man/auto switch must be in the manual position for the 
raise/lower switch to operate.  
 

Summary of Contents for STABILINE WHR22 Series

Page 1: ...to make engineering changes on all its products Such refinements may affect information given in the instructions Therefore USE ONLY THE INSTRUCTIONS THAT ARE PACKED WITH THE PRODUCT WARNING High vol...

Page 2: ...xamine it carefully for any shipping damage The Damage and Shortage instructions packed with the unit outlines the procedure to follow if any parts are missing or damaged 2 0 DESCRIPTION 2 1 GENERAL W...

Page 3: ...nge S Single Control D Double Control T Triple Control LNN Size Code 3 or 4 digits R Rack Cabinet T Tall Cabinet CB Input Circuit Breaker CS Input Circuit Breaker w 120vac Shunt Trip CR Input Circuit...

Page 4: ...mum rated current as specified by local and national code requirements The front panel s of the voltage regulator must be removed to allow access to the input and load terminals To remove a panel use...

Page 5: ...5 2 SETTING OUTPUT VOLTAGE AND SENSITIVITY POTENTIOMETERS Normally the WHR Series voltage regulator should not be operated without the front panel s of the cabinet in place However during the initial...

Page 6: ...eaker if the coil voltage is lost The trip coil is rated 120 volt AC The coil voltage must be present in order to close the circuit breaker 6 2 1 3 Circuit Breaker Trip Coil Alarm Contacts When alarm...

Page 7: ...ged the factory settings and did not select the store option the factory setting can be reinstated by pressing both RECALL buttons at the same time The stored factory settings are shown in the table b...

Page 8: ...ted load current and in some cases the maximum rated nominal input voltage must be reduced Refer to the All Buck and All Boost Rating Chart for the all boost ratings For all boost operation the input...

Page 9: ...ess the unit is overloaded there is little likelihood of component failure Warning Voltages are present inside this unit which can cause injury Therefore only personnel qualified to service electrical...

Page 10: ...e motor at the end of travel If the motor operates successfully in this test the problem may be with the control board 8 10 Inspect the POWERSTAT Variable Transformer brush s and commutator s for sign...

Page 11: ...F38 850 200 1200 INPUT VOLTAGE 240 120 FREQUENCY 50 60 Hz CONNECTION 1 Phase 3 Wire RANGE 20 to 10 of Selected Output OUTPUT VOLTAGE 240 120 CONNECTION 50 60 HZ Model Number base unit Rated Load Max I...

Page 12: ...ilated enclosures intended for indoor use under usual service conditions Temperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to...

Page 13: ...ONTROL MODULE ASSEMBLY A1 Standard Reference Symbol Part Description Part Number A1 CONTROL MODULE 213243 002 A1 A1 CONTROL BOARD 227412 001 A1 F1 F2 F3 F4 FUSE 600V 104364 003 A1 LP1 LP2 LIGHT INDICA...

Page 14: ...n 10 5 AUX POWER MODULE There is one standard power module used throughout this WHR Series of STABILINE Automatic Voltage Regulators It is used for Line to Line connections Line Line Reference Symbol...

Page 15: ...15 11 0 SCHEMATIC For reference only use full size supplied with unit...

Page 16: ...16 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters...

Page 17: ...17 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 19: ...19 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters...

Page 20: ...20 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters...

Page 21: ...21 Enclosures DD through GG Note All dimensions are inches millimeters...

Page 22: ...22 Enclosures DD through GG continues Note All dimensions are inches millimeters...

Page 23: ...23 Enclosures EEE through GGG Note All dimensions are inches millimeters...

Page 24: ...24 Enclosures EEE through GGG continues Note All dimensions are inches millimeters...

Page 25: ...25 13 0 RACK MOUNT DIMENSIONS OPEN Enclosures R1 and R2 Note All dimensions are inches millimeters...

Page 26: ...hich offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are availab...

Reviews: