background image

 

6

6.0. 

OPTIONS

 

 

6.1.  NON DESIGNATED OPTIONS 

 

6.1.1. 

Auxiliary Power Modules

 (A2) 

These modules are provided on units where a 120 volt 
AC  source  is  required  to  operate  internal circuitry. The 
output voltage of these modules is on terminals 1 and 2 
of  the  terminal  strip.  If  there  is  no  output  on  these 
terminals  check  the  two  fuses  mounted  on  the  same 
bracket. The output of the auxiliary power modules are 
used  to  operate  fans,  trip  or  hold  on  circuit  breakers, 
and  on  any  other  applications  where  120  volts  is 
required. 
 

6.1.2. 

Fans

 (B2) 

On  larger  units  fans  are  provided  to  help  efficiently 
remove  heat  generated  in  the  cabinet.  An  auxiliary 
power module supplies the fan operating voltage. If the 
fans  do  not  operate  insure  the  auxiliary  power  module 
output voltage is present. 
 

6.2.  MODEL NUMBER SPECIFIED OPTIONS 

 

6.2.1. 

Circuit Breaker

 (CB1) 

An  input  circuit  breaker  provides  short  circuit  and 
overload  protection  for  the  WHR  Series  Voltage 
Regulators.  Industrial  circuit  breakers  with  high 
interrupting  capacity  are  used.  These  breakers  also 
serve as an on/off switch for the regulator and any load 
attached. 
 

6.2.1.1.  Shunt Trip

 (L1) 

In  unit  where  the  model  number  designates  the  input 
circuit  breaker  as  “CS”  the  circuit  breaker  is  equipped 
with  a  shunt  trip.  A  shunt  trip  causes  the  breaker  to 
open when voltage is applied to the shunt trip coil. The 
trip coil is rated 120 volt, AC and is de-energized when 
the breaker opens. 
 
When  alarm  contact  options  and  a  circuit  breaker  trip 
option  are  ordered  together,  the  unit  is  furnished  with 
120 volt AC, auxiliary power module (A2) and the alarm 
circuit  contacts  are  wired  to  trip  the  input breaker. The 
Shunt  Trip  Connections  Diagram  shows  the  typical 
connections. 
 

6.2.1.2.  Under Voltage Trip

 (L1) 

In  unit  where  the  model  number  designates  the  circuit 
breaker as “CR” the circuit breaker is equipped with an 
under  voltage  release  coil.  This  coil  allows  the  circuit 
breaker to close when voltage is applied and opens the 
breaker  if  the  coil  voltage  is  lost.  The  trip  coil  is  rated 
120 volt, AC. The coil voltage must be present in order 
to close the circuit breaker. 
 
 

6.2.1.3.  Circuit Breaker Trip Coil & Alarm Contacts

 

When  alarm  contact  options  and  a  circuit  breaker  trip 
option  are  ordered  together,  the  unit  is  furnished  with 

120 volt AC, auxiliary power module (A2) and the alarm 
contacts  are  wired  to  trip  the  input  breaker.  A 
momentary  switch  is  provided  to  override  any  alarm 
activation that would trip the circuit breaker. This allows 
turn  on  of  the  system  and  alarm  options to reset. Hold 
switch  in  while  turning  on  the  circuit  breaker.  Alarm 
options  include  frequency  meter  and  input  voltage 
range alarm. 
 
The  following  connection  diagrams  show  typical  shunt 
trip and under voltage release circuits. Circuit shown is 
has a 3 pole circuit breaker but it would be the same for 
a 2 pole circuit breaker. 
 
 

Shunt Trip 

 

Under Voltage Release 

 
 
If  you  do  not  want  the  alarm  contacts  to  trip  the  input 
breaker, the unit can easily be re-configured. 
 
Disable  the  alarms  from  tripping  a  shunt  trip  coil, 
remove  the  120  volts  supplied  by  the  auxiliary  power 
module  to  energize  the  coil.  Removing  the  wires  from 
A2-TB1  terminals  1  and  2  that  connect  to  the  alarm 
switches  and  TB2  does  this.  Do  not  disconnect  any 
other devices from this source. 
 
Disable  the  alarms  from  tripping  an  under  voltage  trip 
coil, by suppling the 120 volts directly to the coil without 
going  through  the  alarm  contacts.  Move  the  wire  on 
TB2-3  that  comes  from  the  auxiliary  power  module  to 
TB2-2 to accomplish this. 
 

6.2.2. 

Delayed Output

 (A5, K2) 

The  delayed output option allows time for the power to 
stabilize 

before 

energizing 

the 

load. 

This 

is 

accomplished  by  adding  a  contactor  and  timer  to  the 
regulator.  When  the  regulator  is  initially  energized:  the 
timer  starts.  After  the  preset  time  delay  the  contactor 
automatically  closes  energizing  the  load.  The  time 
delay  is  field  adjustable  from  approximately  5  to  30 
seconds  and  factory  adjusted  to  approximately  10 
seconds when shipped. 
 
 
 

6.2.3. 

Manual Bypass Switch

 (S3) 

This  two-position  switch,  in  the  REGULATOR  position, 
provides  conditioned  power  from  input  source  through 

Summary of Contents for STABILINE WHR22 Series

Page 1: ...to make engineering changes on all its products Such refinements may affect information given in the instructions Therefore USE ONLY THE INSTRUCTIONS THAT ARE PACKED WITH THE PRODUCT WARNING High vol...

Page 2: ...xamine it carefully for any shipping damage The Damage and Shortage instructions packed with the unit outlines the procedure to follow if any parts are missing or damaged 2 0 DESCRIPTION 2 1 GENERAL W...

Page 3: ...nge S Single Control D Double Control T Triple Control LNN Size Code 3 or 4 digits R Rack Cabinet T Tall Cabinet CB Input Circuit Breaker CS Input Circuit Breaker w 120vac Shunt Trip CR Input Circuit...

Page 4: ...mum rated current as specified by local and national code requirements The front panel s of the voltage regulator must be removed to allow access to the input and load terminals To remove a panel use...

Page 5: ...5 2 SETTING OUTPUT VOLTAGE AND SENSITIVITY POTENTIOMETERS Normally the WHR Series voltage regulator should not be operated without the front panel s of the cabinet in place However during the initial...

Page 6: ...eaker if the coil voltage is lost The trip coil is rated 120 volt AC The coil voltage must be present in order to close the circuit breaker 6 2 1 3 Circuit Breaker Trip Coil Alarm Contacts When alarm...

Page 7: ...ged the factory settings and did not select the store option the factory setting can be reinstated by pressing both RECALL buttons at the same time The stored factory settings are shown in the table b...

Page 8: ...ted load current and in some cases the maximum rated nominal input voltage must be reduced Refer to the All Buck and All Boost Rating Chart for the all boost ratings For all boost operation the input...

Page 9: ...ess the unit is overloaded there is little likelihood of component failure Warning Voltages are present inside this unit which can cause injury Therefore only personnel qualified to service electrical...

Page 10: ...e motor at the end of travel If the motor operates successfully in this test the problem may be with the control board 8 10 Inspect the POWERSTAT Variable Transformer brush s and commutator s for sign...

Page 11: ...F38 850 200 1200 INPUT VOLTAGE 240 120 FREQUENCY 50 60 Hz CONNECTION 1 Phase 3 Wire RANGE 20 to 10 of Selected Output OUTPUT VOLTAGE 240 120 CONNECTION 50 60 HZ Model Number base unit Rated Load Max I...

Page 12: ...ilated enclosures intended for indoor use under usual service conditions Temperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to...

Page 13: ...ONTROL MODULE ASSEMBLY A1 Standard Reference Symbol Part Description Part Number A1 CONTROL MODULE 213243 002 A1 A1 CONTROL BOARD 227412 001 A1 F1 F2 F3 F4 FUSE 600V 104364 003 A1 LP1 LP2 LIGHT INDICA...

Page 14: ...n 10 5 AUX POWER MODULE There is one standard power module used throughout this WHR Series of STABILINE Automatic Voltage Regulators It is used for Line to Line connections Line Line Reference Symbol...

Page 15: ...15 11 0 SCHEMATIC For reference only use full size supplied with unit...

Page 16: ...16 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters...

Page 17: ...17 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 19: ...19 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters...

Page 20: ...20 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters...

Page 21: ...21 Enclosures DD through GG Note All dimensions are inches millimeters...

Page 22: ...22 Enclosures DD through GG continues Note All dimensions are inches millimeters...

Page 23: ...23 Enclosures EEE through GGG Note All dimensions are inches millimeters...

Page 24: ...24 Enclosures EEE through GGG continues Note All dimensions are inches millimeters...

Page 25: ...25 13 0 RACK MOUNT DIMENSIONS OPEN Enclosures R1 and R2 Note All dimensions are inches millimeters...

Page 26: ...hich offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are availab...

Reviews: