background image

 

10

8.8. 

If  the  motor  continues  to  hum  or  buzz  after  the 

OUTPUT  VOLTAGE  RANGE  switch  is  turned  off,  the 
solid-state  switch  controlling  the  motor  may  be 
defective.  De-energize  the  input  line  to  the  voltage 
regulator, and replace the control board. 
 

8.9. 

If  the  motor  has  driven  to  one  end  or  does  not 

drive  at  all,  check  to  ensure  the  motor  drive  is 
functioning  correctly.  Refer  to  the  unit's  schematic 
diagram to complete the following steps: 
 
De-energize  the  input  line  to  the  voltage  regulator; 
place  the  OUTPUT  VOLTAGE  RANGE  switch  in  the 
center (off) position, and remove POWER fuses F1 and 
F2 on each control module. 
 
Apply  115  volts  AC  between  terminals  A1-TB1-1  and 
A1-TB1-2  on  the  control  module,  or  to  the 
corresponding  terminals  at  the  motor  board  terminal 
strip  (TB1).  These  nine  junction  terminal  strips  are 
connected  point-for-point.  The  motor  should  turn  the 
variable  transformer  counter  clockwise  (viewed  from 
top)  so  as  to  lower  the  output  voltage  until  it  reaches 
the end of its travel, where the limit switch will prevent 
further rotation in that direction. 
 
Apply  115  volts  between  terminals  A1-TB1-1  and 
A1-TB1-3 should run the motor in the opposite direction 
until a limit switch stops the motor at the end of travel. 
 
If  the  motor  operates  successfully  in  this  test  the 
problem may be with the control board. 

 

8.10. 

Inspect  the  POWERSTAT  Variable  Transformer 

brush(s)  and  commutator(s)  for  signs  of  wear  or 
damage.  The  brush  assemblies  on  the  variable 
transformer  section  will  not  need  replacement  under 
normal  conditions.  When  excessive  brush  wear  or 
commutator  damage  occurs,  it  is  usually  the  result  of 
an 

overload. 

If 

either 

condition 

exists, 

the 

POWERSTAT  Variable  Transformer  section  or  the 
brush  must  be  replaced  or  repaired.  Check  the  load to 
be  sure  the  output  current  rating  of  the  voltage 
regulator is not being exceeded. 
 

Do  not  attempt  to  clean  a  commutator  with  an 
abrasive  such  as  sandpaper  or  a  file. 

This  will  ruin 

the  soft  precious  metal  plating  on  the  commutator 
surface and will shorten the life of the unit. It is normal 
for  commutators  to  become  black  due  to carbon brush 
tracking.  If  a  commutator  is  to  be  cleaned,  use 
denatured alcohol and a soft cloth. 
 

8.11. 

Check  the  variable  transformer  radiator(s)  (the 

die cast part that holds the brush assembly) for signs of 
slippage,  and  see  if  all  brushes  driven  by  the  same 
motor are aligned with each other. The alignment of the 
radiator  and  brushes  depends  on  the  setscrews  that 
hold the variable transformer center tube(s) to the shaft 
and  the  setscrews  that  hold  the  radiator  to  the  center 
tube. Adjust and tighten as needed. 

Summary of Contents for STABILINE WHR22 Series

Page 1: ...to make engineering changes on all its products Such refinements may affect information given in the instructions Therefore USE ONLY THE INSTRUCTIONS THAT ARE PACKED WITH THE PRODUCT WARNING High vol...

Page 2: ...xamine it carefully for any shipping damage The Damage and Shortage instructions packed with the unit outlines the procedure to follow if any parts are missing or damaged 2 0 DESCRIPTION 2 1 GENERAL W...

Page 3: ...nge S Single Control D Double Control T Triple Control LNN Size Code 3 or 4 digits R Rack Cabinet T Tall Cabinet CB Input Circuit Breaker CS Input Circuit Breaker w 120vac Shunt Trip CR Input Circuit...

Page 4: ...mum rated current as specified by local and national code requirements The front panel s of the voltage regulator must be removed to allow access to the input and load terminals To remove a panel use...

Page 5: ...5 2 SETTING OUTPUT VOLTAGE AND SENSITIVITY POTENTIOMETERS Normally the WHR Series voltage regulator should not be operated without the front panel s of the cabinet in place However during the initial...

Page 6: ...eaker if the coil voltage is lost The trip coil is rated 120 volt AC The coil voltage must be present in order to close the circuit breaker 6 2 1 3 Circuit Breaker Trip Coil Alarm Contacts When alarm...

Page 7: ...ged the factory settings and did not select the store option the factory setting can be reinstated by pressing both RECALL buttons at the same time The stored factory settings are shown in the table b...

Page 8: ...ted load current and in some cases the maximum rated nominal input voltage must be reduced Refer to the All Buck and All Boost Rating Chart for the all boost ratings For all boost operation the input...

Page 9: ...ess the unit is overloaded there is little likelihood of component failure Warning Voltages are present inside this unit which can cause injury Therefore only personnel qualified to service electrical...

Page 10: ...e motor at the end of travel If the motor operates successfully in this test the problem may be with the control board 8 10 Inspect the POWERSTAT Variable Transformer brush s and commutator s for sign...

Page 11: ...F38 850 200 1200 INPUT VOLTAGE 240 120 FREQUENCY 50 60 Hz CONNECTION 1 Phase 3 Wire RANGE 20 to 10 of Selected Output OUTPUT VOLTAGE 240 120 CONNECTION 50 60 HZ Model Number base unit Rated Load Max I...

Page 12: ...ilated enclosures intended for indoor use under usual service conditions Temperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to...

Page 13: ...ONTROL MODULE ASSEMBLY A1 Standard Reference Symbol Part Description Part Number A1 CONTROL MODULE 213243 002 A1 A1 CONTROL BOARD 227412 001 A1 F1 F2 F3 F4 FUSE 600V 104364 003 A1 LP1 LP2 LIGHT INDICA...

Page 14: ...n 10 5 AUX POWER MODULE There is one standard power module used throughout this WHR Series of STABILINE Automatic Voltage Regulators It is used for Line to Line connections Line Line Reference Symbol...

Page 15: ...15 11 0 SCHEMATIC For reference only use full size supplied with unit...

Page 16: ...16 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters...

Page 17: ...17 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters...

Page 19: ...19 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters...

Page 20: ...20 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters...

Page 21: ...21 Enclosures DD through GG Note All dimensions are inches millimeters...

Page 22: ...22 Enclosures DD through GG continues Note All dimensions are inches millimeters...

Page 23: ...23 Enclosures EEE through GGG Note All dimensions are inches millimeters...

Page 24: ...24 Enclosures EEE through GGG continues Note All dimensions are inches millimeters...

Page 25: ...25 13 0 RACK MOUNT DIMENSIONS OPEN Enclosures R1 and R2 Note All dimensions are inches millimeters...

Page 26: ...hich offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are availab...

Reviews: