SUNX Limited MJE-SF4B01 No.0005-03V
-
41
-
2-5-5 Wiring for Manual Reset (Interlock is Valid)
(Wiring Example of the Control Category 4)
This is the general configuration using one set of the emitter and receiver facing each other.
The control output (OSSD 1, OSSD 2) turns OFF if the light is blocked.
<For PNP output>
Interlock function
Valid (Manual reset)
External device monitor function
Valid
Auxiliary output
Can be used
Notes: 1) Vs is the applying supply voltage.
2) The circuit diagram shown above is for 12-core cable to be used. For 8-core cable, red, yellow, grey, grey /
black, sky-blue / white, sky-blue / black, there is no lead wire.
3) For resetting, refer to ‘
3-2 Interlock Function
’.
The sensor output is selected depending on the connecting state of the shield wire. Incorrect wiring may cause the
lockout state.
* Symbols
Switch S1
Vs to Vs - 2.5V (sink current 5mA or less): Emission halt (Note 1), Open: Emission
K1, K2: External device (Forced guided relay or magnetic contactor)